Fault
Fault
Message
code
24
Speed fault
Fan
26
Fan fault
27
Faulty stratification
sensor
29
Differential pressure
sensor short circuit
30
CRC
Burner control unit
34
CRC BCC-ID incorrect
in CM-EEPROM
35
BCC not correct
36
CRC BCC-ID incorrect
in the BCC
37
Incorrect BCC
38
BCC update required – Boiler coding card fault, PCB
39
BCC system error
42
Condensate pump not
pumping
52
max. cylinder heating
time
78
Header sensor fault
85
Relay test
90
BCU communication
91
Bus communication
95
Prog. mode
96
Reset
99
System error
Burner control unit
3066501_201910
Cause
– Set fan speed is not achieved.
– The fan does not stop.
– Faulty stratification cylinder
sensor or lead.
– Differential pressure sensor
or cable defective.
– The EEPROM data set is invalid. ► Switch power supply OFF/ON.
– Boiler coding card fault.
– Boiler coding card has been
removed or incorrectly inserted.
– Boiler coding card fault.
– The boiler coding card is
incompatible with the burner
control unit.
requires a new boiler coding card
(if replacement part).
– Boiler coding card fault
– Condensate pump is defective.
– Drain line is blocked.
– No power supply to the
condensate pump.
– The cylinder heat time lasts longer
than permitted.
– Faulty header sensor or lead.
– Relay test failed.
– Emergency stop via ChipCom.
– Communication between control
unit PCB and burner control unit
disrupted.
– Duplicated eBus address.
– Burner control unit is controlled
by PC.
– Reset button pressed too many
times.
– Internal burner control unit fault.
Remedy
► Press reset button.
► Switch power supply OFF/ON.
► Check power cable to fan.
► Check fan.
► Check power cable to fan.
► Check fan.
► Press reset button.
► Check sensor.
► Check lead.
► Test sensor.
► Check lead.
► Press reset button.
If fault persists:
► change burner control units.
► Replace boiler coding card.
► Refit the correct boiler coding
card.
► Replace boiler coding card.
► Insert the correct boiler coding
card.
► Press reset button.
► Reinsert boiler coding card.
► Check boiler coding card.
► Replace boiler coding card.
► Check the condensate pump.
► Check drain line.
► Check power connector and
fuses.
► Check DHW sensor (cylinder
sensor) and sensor lead.
► Vent cylinder.
► Extend cylinder heating time.
Press reset button.
► Check sensor.
► Check lead.
► Switch power supply OFF/ON.
► Press reset button.
► Press reset button.
► Check connection between
burner control unit and HCM-2
board.
► Assign the eBus address once.
No action.
► Switch power supply OFF/ON.
► Switch power supply OFF/ON.
WOLF GmbH | 67