Heating Water - Wolf COB-2 Operation Instructions Manual

Oil condensing boiler for central heating with stratification cylinder
Table of Contents

Advertisement

Planning
4.3.2

Heating water

Limits
Limits
(Table
Complied with
Not complied with
Table 4.2
Treatment of heating water in accordance with VDI 2035
Heating water additives
NOTE
Heating water additives!
Damage to heating water heat exchanger.
► Do not use antifreeze or inhibitors.
NOTE
Corrosion of aluminium components due to pH levels being too high or too low!
Damage to heating water heat exchanger
► The pH value of the heating water must be between 6.5 and 9.0.
► In mixed installations, a pH value of 8.2 to 9.0 must be maintained in accordance with VDI 2035.
Electrical conductivity and water hardness
The limits for conductivity and water hardness are dependent on the specific system volume V
(V
= system volume / max. rated heating output).
A
According to VDI 2035, in systems with multiple boilers, use the maximum rated heating output of the
smallest heat generator.
Heating water quality requirement relating to the entire heating system:
Total heating output
[kW]
≤ 50
50-200
Total heating output
[kW]
≤ 50
50-200
Total heating output
[kW]
≤ 50
50-200
Total hardness conversion: 1 mol/m³ = 5.6 °dH = 10 °fH
1
< 800 µS/cm: high salinity / < 100 µS/cm: low salinity
2
< 0.11 °dH recommended standard, permissible up to limit of < 1 °dH
3
Table 4.3
Electrical conductivity and water hardness
3066501_201910
Measures
4.3)
Use potable water as fill and top-up water.
Flush system with potable water.
This water must be desalinated
using a dirt filter upstream from the ion
exchanger.
Total hardness
≤ 16.8
Total hardness
Total hardness
≤ 0.11
≤ 0.11
V
/ total alkaline earths
1
[°dH]
≤ 11.2
V
> 20 L/kW and < 50 L/kW
A
/ total alkaline earths
1
[°dH]
≤ 11.2
≤ 8.4
V
/ total alkaline earths
1
[°dH]
3
3
Possible consequences of
failing to follow instructions
-
High level of oxygen ingress
Warranty voided for water-side
system components.
≤ 20 L/kW
A
Conductivity
[mol/m³]
≤ 3.0
≤ 2
Conductivity
[mol/m³]
≤ 2
≤ 1.5
≥ 50 L/kW
A
Conductivity
[mol/m³]
≤ 0.02
≤ 0.02
A
at 25°C
2
Cond. [µS/cm]
< 800
< 100
at 25°C
2
Cond. [µS/cm]
< 800
< 100
at 25°C
2
Cond. [µS/cm]
< 800
< 100