Connecting The Balanced Flue; Installing The Balanced Flue - Wolf COB-2 Operation Instructions Manual

Oil condensing boiler for central heating with stratification cylinder
Table of Contents

Advertisement

Installation
5.9
Connecting the balanced flue
► Comply with the planning guidance
Fig. 5.14
Example: balanced flue [mm]
Heat generator
q
Appliance connection with flue gas test port
w
Inspection piece
e
5.9.1
Installing the balanced flue
Installation information for balanced flue system
NOTE
Inadequate incline for balanced flue!
Corrosion of components or faults.
► Install the balanced flue with an angle of at least 3° (6 cm/m) relative to the heat generator.
► Follow the installation instructions for the balanced flue system.
► Never install damaged parts.
► Create flue connections using sockets and gaskets.
► Ensure that gaskets are fitted correctly.
► Always arrange sockets against the direction of the condensate flow.
► Always trim the flue on the smooth side, never on the coupling side.
► Bevel or deburr trimmed flues to ensure gas-tight installation of pipe joints.
► Remove contamination before installation.
► Wet or lubricate all air/flue gas joints prior to installation, e.g. using soap suds or a suitable grease
without silicone.
► Lines must be secured with brackets.
Connecting the appliance connection with flue gas test port
► Install appliance connection with flue gas test port (2)
connection point of the heat generator (1).
Fit inspection piece
If an inspection aperture is required for the balanced flue,
► insert a balanced flue pipe with inspection aperture.
38 | WOLF GmbH
4.6 Air/flue gas
routing.
y
r
DN60/100: 235
t
DN80/125: 200
r
e
w
q
Balanced pipe flue
r
Disconnect device
t
Spacer clip
y
(Fig. 5.14 Example: balanced flue
[mm]) at the
3066501_201910