Fault
Fault
Message
code
107
HC pressure
Table 8.1
Fault messages
8.4.2

Warning messages

Warning messages do not lead directly to the heat generator being switched OFF. The issue which
caused the warning may lead to malfunctions or faults.
► These issues must be rectified by a contractor.
Warning
Message
codes
4
No flame
5
Flame failure
22
Differential pressure
sensor not responding
23
Differential
pressure sensor not
deactivating
24
Speed fault
Fan
26
Fan fault
107
HC pressure
Table 8.2
Warning messages
68 | WOLF GmbH
Cause
– System pressure too low.
– Supply line pressure sensor faulty.
– Pressure sensor faulty.
Cause
– When the burner starts, no
flame forms by the end of
safety time.
– Ignition electrodes
contaminated.
– Air in the oil feed line.
– Heat generator contaminated
– Flame failure during operation.
– Flue gas return system (flue
gas in the supply air).
– Air in the oil feed line.
– Heat generator contaminated.
– Differential pressure too low in
pre-purge phase.
– Differential pressure sensor or
cable defective.
– Differential pressure sensor
fails to switch back.
– Set fan speed is not achieved. ► Check power cable to fan.
– The fan does not stop.
– System pressure too low.
– Supply line pressure sensor
faulty.
– Pressure sensor faulty.
Remedy
► Check system pressure.
► Check if supply line is faulty.
► Check pressure sensor cables
and plug-in connections.
If OK but no function:
► Replace pressure sensor.
► Press reset button.
Remedy
► Check oil line and oil level.
► Check ignition electrodes and
ignition transformer.
► Check solenoid valve for oil
pump.
► Check that the condensate can
drain off freely.
► Press reset button.
► Check CO
values.
2
► Service the equipment.
► Check flue system for leaks.
► Check oil line and oil level.
► Press reset button.
► Check CO
values.
2
► Service the equipment.
► Check supply air and flue gas
path.
► Check differential pressure
sensor.
► Check lead.
► Check differential pressure
sensor.
► Check fan.
► Press reset button.
► Check power cable to fan.
► Check fan.
► Press reset button.
► Check system pressure.
► Check if supply line is faulty.
Pressure sensor:
► Check cables and plug-in
connections. If OK but no
function:
► Replace pressure sensor.
► Press reset button.