Heating System; Fuel Supply - Wolf COB-2 Operation Instructions Manual

Oil condensing boiler for central heating with stratification cylinder
Table of Contents

Advertisement

Planning
4.7.3

Heating system

Heating circuit
The following types of connections shall be selected to ensure the heating water flow rate through every
heat generator is as even as possible:
– For precise hydronic balancing, fit a line regulating valve in the supply line to every heat generator.
– Design the flow and return lines with the same length for the flow and return according to the
Tichelmann system to ensure the pressure drop in every line is equally high.
Low loss header
It must not be possible for the on-site heating circuit pumps or primary pumps to influence the function of
the heat generator. A low loss header should therefore be installed upstream of the heating water circuit
or DHW cylinder circuit.
Ensure that the heating water flow rate through the heat generator is set lower than that through the
subsequent heating circuit. The flow rate should be set upstream of the low loss header via a line
regulating valve or butterfly valve.
Hydraulic separation
Instead of the low loss header, a heat exchanger can be installed. If pipes are used which are not
impermeable to oxygen, this is a requirement in any case.
4.7.4

Fuel supply

The oil lines must be sized in accordance with TRÖl.
Each heat generator must be provided with its own oil supply.
If there is only one oil storage installation, this supply must be arranged centrally via a suction unit.
The suction unit must be installed as close to the boiler cascade as possible.
q
Fig. 4.8
Fuel supply
Oil storage installation
q
3066501_201910
w
w
Suction unit
WOLF GmbH | 27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cob-2-ts

Table of Contents