Installation
Fit disconnect device
► Slide the disconnect device (6)
► Slide the next balanced flue pipe (5) 50 mm into the socket of the disconnect device (6).
► Ensure that the balanced flue pipe (5) is fully secured in this position, e. g. with a pipe clamp (7) or with
a locking screw on the air side.
Calculating clearance and offset
Fig. 5.15
Balanced flue pipe length
A
Clearance
B
Offset
Balanced flue pipe length
q
► Determine distance (A).
► Balanced flue pipe (1) length always approximately 100 mm longer than clearance (A).
► Take the offset (B) into account.
Bend
87°
45°
Table 5.1
Offset bend
Installing a balanced flue in an existing chimney/duct
► Make sure that there is appropriate clearance between the outside of the flue and the wall of the duct
(Fig. 4.6 Minimum shaft size
► Flue lines, retaining straps and spacers must be installed in channels and ducts in such a way that the
ventilated cross-section can be inspected and cleaned.
► Close cleaning apertures in ducts with chimney cleaning covers which have been assigned an
approved test mark.
► The outlets of flue lines in ducts must be designed so that the following requirements are met:
– no ingress of precipitation
– secondary ventilation can flow freely
► It must be possible to remove removable covers without tools and they must be secured to prevent
them falling.
3066501_201910
(Fig. 5.14 Example: balanced flue
w
A
q
e
w
B
At least 204 mm
At least 93 mm
[mm]).
[mm]) fully into the socket (5).
A
e
q
45° bend
w
Bend 87°
e
w
w
B
WOLF GmbH | 39