Permitted Connection Types; Air/Flue Gas Routing Lengths - Wolf COB-2 Operation Instructions Manual

Oil condensing boiler for central heating with stratification cylinder
Table of Contents

Advertisement

Planning
4.6.3

Permitted connection types

Type
Appliance type
Operating mode
Open flue
Room sealed
Can be connected to
Moisture-resistant chimney
Balanced flue chimney
Air/flue gas routing
Certified air/flue gas routing
Moisture-resistant flue
An x indicates that all components of the flue are surrounded by combustion air and meet higher requirements for gas tightness.
1
For types B23 and B33, the combustion air is drawn from the installation room (open flue combustion equipment).
2
For type C, the combustion air is drawn through a sealed system from the outside (room sealed combustion equipment).
3
Table 4.8
Permitted connection types
The following balanced flues or standard flues with CE-0036-CPD-9169003 certification may be used
(Table 4.9 Permissible air/flue gas routing lengths
– Flue DN60
– Concentric balanced flue DN60/100
– Flexible flue DN60
– Flue DN80
– Concentric balanced flue DN80/125
– Concentric balanced flue (on an external wall)
DN80/125
The necessary type plates and certificates are included with the relevant WOLF accessories.
4.6.4
Air/flue gas routing lengths
The calculation was made taking the pressure conditions into account (geodetic height: 325 m). The
specified lengths refer to concentric balanced flues and standard flues and apply to original WOLF
components only.
Maximum length
Type Design variants
Flue in a shaft and combustion air directly via heat
B23
generator (open flue)
Flue in a shaft with horizontal, concentric connecting
B33
pipe (open flue)
Connection to a moisture-resistant flue gas chimney
B33
with a horizontal concentric connection pipe (open
flue)
Vertical concentric roof outlet through pitched or flat
C33x
roof, vertical concentric balanced flue system for
installation in a shaft (room sealed)
Connection to a moisture-resistant balanced flue
C43x
chimney, maximum pipe length from centre of bend
on heat generator to connection 3 m (room sealed)
Connection to the flue in a shaft and supply air pipe
C53
through an external wall (room sealed, supply air
pipe 4 m, 1x bend 87°)
Connection to a flue on an external wall (room
C53x
sealed)
22 | WOLF GmbH
1, 2, 3
COB-2-15/20/29/40
B23, B33, C33x, C43x, C53, C53x, C63x, C83x, C93x
Yes
Yes
B23, B33, C83x
C43x
C33x, C53x, C93x
C63x
B23, C53x, B33
[m]):
– Flexible flue DN83
– Flue DN110
– Flexible flue DN 110
– Concentric balanced flue DN110/160
– Flue DN 160 (for cascade operation)
COB-2
DN 60
DN 80
DN 110
DN 60
DN 80
DN 110
DN 60/110
DN 80/125
DN 110/160
DN 80/125
DN 110/160
DN 80/125
DN 110/160
Maximum length [m]
15
20
29
20
-
-
30
30
30
-
-
-
18
-
-
30
30
30
-
-
Calculation according to DIN
EN 13384 (balanced flue
chimney manufacturer)
9
-
-
24
22
18
-
-
-
Calculation according to DIN
EN 13384 (balanced flue
chimney manufacturer)
30
30
30
-
-
-
30
30
30
-
-
-
3066501_201910
1
40
-
-
30
-
-
30
-
-
14
-
30
-
30