Page 1
Tracer CH535 Chiller Controller on models CGAX/CXAX July 2020 CG-SVU007D-GB Confi dential and proprietary Trane information Original instructions...
FWD 10 even merely suspected, notify the carrier within 24 hours by registered letter. Notify the local Trane Sales office at the same time. The unit should be totally inspected within 3 days of delivery. If damage is observed, notify the last carrier FWD 12 by registered letter and notify the local sales office.
Tracer CH535 Presentation Technical Data Important note: This document describes all the functions available on TRACER CH535 with software version 1.x and explains how to program it. Certain parameters must only be modified by qualified personnel. Before changing any parameter, always check that the change does not affect the good and safe operation of the equipment.
Tracer CH535 Extention Hardware Figure 3 – CH535 extention terminal locations Sound power levels Discharge Measurement conditions: Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m long) fixed to its discharge opening.
Tracer CH535 module connections Terminals Technical Data TRACER CH535 offers customer the possibility to use inputs or outputs in order to: • use an external water setpoint reset using an analog input (option), • use an auxiliary setpoint (option), • connect a remote on/off of the circuit/unit (standard), •...
Alarms Alarms display and resetting A fault on a unit will be shown through the user interface or through 2 digital outputs, one for each refrigerant circuit. The alarms are divided into 3 categories: Warning: Shows that something is wrong on the unit but unit can be kept in operation. A message is displayed on Sound power levels the user interface screen.
Alarms Technical Data Table 4 – Status, Warning and Alarm messages Reset N° Message Unit Status Description Type No Alarm Unit On See unit status on Main display Power supply (V/Ph/Hz) 230/1/50 Alarm Water Pump1 Manual Unit On Defective water pump 1 Capacities Alarm Water Pump2 Manual...
Page 11
Alarms Reset N° Message Unit Status Description Type Ckt2 Defrost Unit On Defrost on Circuit 2 Loss of water flow for more than 1 sec. Pump Sound power levels Alarm Loss of Water Flow Auto Unit Off restarts by a manual unit mode changeover Faulty sensor, out of range -30..+80°C Discharge Alarm Air Sensor...
Page 12
Alarms Technical Data Reset N° Message Unit Status Description Type Warning Comp.1A Manual Unit On Maintenance Warning Comp.1B Power supply (V/Ph/Hz) 230/1/50 Manual Unit On Capacities Maintenance Cooling capacity on water (1) (kW) 18,8 30,1 Compressor running hours above the threshold Warning Comp.1C Heating capacity on water (2) (kW)
Page 13
Alarms Reset N° Message Unit Status Description Type Alarms pCOe 5 IO Auto Unit On pCOextension5 is in default on Analog input #4 mismatch Sound power levels Alarm Drive Fault Manual Unit Off Variable Primary Flow Drive fault Alarm Low Differential Low Differential Pressure on circuit 1 (High Discharge Auto...
User interface display Technical Data Figure 4 – LCD Display Power supply (V/Ph/Hz) 230/1/50 Capacities Cooling capacity on water (1) (kW) 18,8 30,1 Heating capacity on water (2) (kW) 11,9 18,9 20,9 38,2 Fan motor (type) 2 x direct drive centrifugal Fan power input (3) (kW) 0,23...
Page 15
User interface display Figure 5 – Deluxe touchscreen display Sound power levels Discharge Measurement conditions: Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m long) fixed to its discharge opening. Power level in dB(A), per Hz frequency band Overall power Unit...
30,1 Unit configuration sub-menu Heating capacity on water (2) (kW) 11,9 18,9 20,9 38,2 (accessible to Trane technicians only, not accessible to end users) Fan motor (type) 2 x direct drive centrifugal Fan power input (3) (kW) 0,23 0,46 0,65...
(from 9:00 to 15:00). Occupied zone from 6:00 to 21:00. FWD 10 Configuration menu FWD 12 Shows and allows modification of unit configuration with 2 user levels (Local technician and Trane service technician): FWD 14 Local technician (by default password = 0005) allows to:...
Notes Technical Data Power supply (V/Ph/Hz) 230/1/50 Capacities Cooling capacity on water (1) (kW) 18,8 30,1 Heating capacity on water (2) (kW) 11,9 18,9 20,9 38,2 Fan motor (type) 2 x direct drive centrifugal Fan power input (3) (kW) 0,23 0,46 0,65 1,04...
Page 19
Notes Sound power levels Discharge Measurement conditions: Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m long) fixed to its discharge opening. Power level in dB(A), per Hz frequency band Overall power Unit speed...
Page 20
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.