7.3

Diagnostics Based on the "BF" LED

7.3.1

"BF" LED with PROFIBUS DP

"BF" LED
Meaning if an Error
Occurs
on
VS 130-2/VS 130-2vcr is
not exchanging data but is
detecting the transmission
rate
flashes
VS 130-2/VS 130-2vcr is
neither exchanging data
nor detecting the
transmission rate
7.3.2

"BF" LED with PROFINET IO

"BF" LED
Meaning if an Error Occurs
on
Bus problem (no physical connection to a
subnet/switch)
Wrong transmission speed
Full duplex transmission is not activated
flashes
Bus communication via PROFINET is
interrupted.
IP address is incorrect.
Incorrect configuration
Incorrect configuration
Incorrect or missing device name
IO controller not available/switched off but
Ethernet communication exists
Vision Sensor SIMATIC VS 130-2/VS 130-2vcr
A5E00475759-01
Possible Remedies
Check that the bus connector is correctly inserted.
Check that there is no break on the bus cable to the DP
master.
If you use an S7 DP master: Check the diagnostic buffer of
the DP master or the slave diagnostic information in
HW Config.
Check the cable lengths relative to the transmission rate.
Check the settings of the terminating resistors.
Check the configuration of the DP master (PROFIBUS
address, transmission rate, configuration, bus profile).
If you use an S7 DP master: Check the diagnostic
buffer of the DP master or the slave diagnostic
information in HW Config.
Possible Remedies
Check that the bus connector is correctly
inserted.
Diagnostics
Check if the IP address or device
name is duplicated on the network.
Check the settings of the I/O
controller.
7-11