7.3
Diagnostics Based on the "BF" LED
7.3.1
"BF" LED with PROFIBUS DP
"BF" LED
Meaning if an Error
Occurs
on
VS 130-2/VS 130-2vcr is
not exchanging data but is
detecting the transmission
rate
flashes
VS 130-2/VS 130-2vcr is
neither exchanging data
nor detecting the
transmission rate
7.3.2
"BF" LED with PROFINET IO
"BF" LED
Meaning if an Error Occurs
•
on
Bus problem (no physical connection to a
subnet/switch)
•
Wrong transmission speed
•
Full duplex transmission is not activated
•
flashes
Bus communication via PROFINET is
interrupted.
•
IP address is incorrect.
•
Incorrect configuration
•
Incorrect configuration
•
Incorrect or missing device name
•
IO controller not available/switched off but
Ethernet communication exists
Vision Sensor SIMATIC VS 130-2/VS 130-2vcr
A5E00475759-01
Possible Remedies
•
Check that the bus connector is correctly inserted.
•
Check that there is no break on the bus cable to the DP
master.
•
If you use an S7 DP master: Check the diagnostic buffer of
the DP master or the slave diagnostic information in
HW Config.
•
Check the cable lengths relative to the transmission rate.
•
Check the settings of the terminating resistors.
•
Check the configuration of the DP master (PROFIBUS
address, transmission rate, configuration, bus profile).
If you use an S7 DP master: Check the diagnostic
•
buffer of the DP master or the slave diagnostic
information in HW Config.
Possible Remedies
Check that the bus connector is correctly
inserted.
•
•
Diagnostics
Check if the IP address or device
name is duplicated on the network.
Check the settings of the I/O
controller.
7-11