Control Register - Delta DVP04PT-S Instruction Sheet

Temperature measurement module
Hide thumbs Also See for DVP04PT-S:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

DVP06PT-S
Overall accuracy
Response time
Isolation method
Digital data format
Average function
Self diagnostic function
RS-485 Communication
Mode
 Control Register
CR# Address Latched Attribute
#0
H'4064
O
#1
H'4065
X
H'4066
#2
O
--
#3
H'4067
O
#4
H'4068
O
#5
H'4069
O
#6 H'406A
X
#7 H'406B
X
Celsius (°C)
0.6% of full scale during 0 ~ 55°C (32 ~ 131°F)
DVP04PT-S: 200ms/channel; DVP06PT-S: 160/ms/channel
Isolation between digital and analog circuitry. There is no isolation
between channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
2's complement of 16-bit
Yes (DVP04PT-S: CR#2 ~ CR#5 / DVP06PT-S: CR#2)
Every channel has the upper/lower limit detection function.
Supported, including ASCII/RTU mode. Default communication
format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the
communication format.
Note1: RS-485 cannot be used when connected to CPU series
PLCs.
Note2: The communication format can only be changed via
RS-485 and cannot be changed via the instruction TO while
connected to CPU series PLCs. Refer to Communication Format
Setup in the appendix of the DVP programming manual for more
details.
Register content
Model name
R
(Set up by the system)
R/W
CH1~CH4 Mode setting
DVP04PT-S:
CH1 average number
R/W
DVP06PT-S:
CH1~CH6 average
number
DVP04PT-S:
H'4067
CH2 average number
DVP04PT-S:
H'4068
CH3 average number
DVP04PT-S:
H'4069
CH4 average number
R
CH1 average degrees
R
CH2 average degrees
DVP04PT-S model code= H'8A
DVP06PT-S model code = H'CA
b15~12
Take CH1 mode (b3,b2,b1,b0)
for example.
1. (0,0,0,0): Pt100 (default)
2. (0,0,0,1): Ni100
3. (0,0,1,0): Pt1000
4. (0,0,1,1): Ni1000
5. (0,1,0,0): LG-Ni1000
6. (0,1,0,1): Cu100
7. (0,1,0,0): Cu50
8. (1,1,1,1): The channel is
disabled.
Number piece of readings used
for the calculation of "average"
temperature on CH1.
Setting range: K1~K20.
Default setting is K10.
Number piece of readings used
for the calculation of "average"
temperature on CH1 ~ 6.
Setting range: K1~K20.
Default setting is K10.
Number piece of readings used
for the calculation of "average"
temperature on CH2.
Setting range: K1~K20.
Default setting is K10.
Number piece of readings used
for the calculation of "average"
temperature on CH3.
Setting range: K1~K20.
Default setting is K10.
Number piece of readings used
for the calculation of "average"
temperature on CH4.
Setting range: K1~K20.
Default setting is K10.
DVP04PT-S:
Average degrees for CH1 ~ 4
- 3 -
Fahrenheit (°F)
Description
b11~8
b7~4
CH4
CH3
CH2
b3~0
CH1