4. I/O terminals
7. Specification label
10. DIN rail (35mm)
13. Power connection port
(DVP04PT-S)
 I/O Terminal Layout
DVP04PT-S
CH1
L+
L-
I-
FG
DVP06PT
CH1
L+
L-
I-
L+
 External Wiring
2 -Wi re
3-Wire
Note1: Use only the wires that are packed with the temperature sensor for analog input and
separate from other power line or any wire that may cause noise.
Note2: 3-wire RTD sensor provides a compensation loop that can be used to subtract the wire
resistance while 2-wire RTD sensor has no mechanism to compensate.
Note3: If there is noise, please connect the shielded cables to the system earth point, and then
ground the system earth point or connect it to the distribution box.
Note4: Please keep wires as short as possible when connecting the module to a device whose
temperature is going to be measured, and keep the power cable used as far away from
the cable connected to a load as possible to prevent noise interference.
Note5: Please connect
system ground, and then ground the system ground or connect the system ground to a
distribution box.
 Electrical Specifications
Max. rated power
consumption
Operation/storage
Vibration/shock
resistance
Series connection to
DVP-PLC MPU
 Functional Specifications
DVP06PT-S
Analog input channel
Sensors type
Current excitation
Temperature input range Please refer to the temperature/digital value characteristic curve.
Digital conversion range
Resolution
5. I/O point indicator
8. I/O module connection port 9. I/O module clip
11. I/O module clip
14. I/O connection port
Ch2
L+
L-
I-
FG
CH3
CH2
L-
I-
L+
L-
Pt100 0
Shielded c able*1
Pt100
S hielded cable* 1
on a power supply module and
2W
Operation: 0°C~55°C (temp.), 5~95% (humidity), pollution degree
2
Storage: -25°C~70°C (temp.), 5~95% (humidity)
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
The modules are numbered from 0 to 7 automatically by their
distance from MPU. No.0 is the closest to MPU and No.7 is the
furthest. Maximum 8 modules are allowed to connect to MPU and
will not occupy any digital I/O points.
Celsius (°C)
6 channels per module
2-wire/3-wire Pt100 / Pt1000 3850 PPM/°C (DIN 43760 JIS
C1604-1989) / Ni100 / Ni1000 / LG-Ni1000 / Cu100 / Cu50
1.53mA / 204.8uA
Please refer to the temperature/digital value characteristic curve.
16 bits (0.1°C)
Ch3
L+
L-
I-
FG
CH4
I-
L+
L-
I-
CH 1
L+
L-
I -
AG
CH6
L +
L-
I-
AG
16 bits (0.1°F)
- 2 -
6. Mounting holes
12. RS-485 communication
port (DVP04PT-S)
Ch4
L+
L-
I-
CH5
L+
L-
I-
L+
[ Figure 2 ]
,
* 2
*2
on the temperature module to a
Fahrenheit (°F)
FG
CH6
L-
I-