………………………………………………………………… ENGLISH ………………………………………………………………… Thank you for choosing DELTA DVP PLC Series. DVP08TC-H2 is able to receive 8 points 0~150mV voltage input of thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type, E-type, N-type) and convert them into 24-bit digital signals.
External Wiring Shielded Thermocouple cable *1 AGN D AGN D Shielded Thermocouple cable *1 Cold-Junction Compensation Terminal of power module A+5V DC/ DC System Converter gr ounding Class 3 grounding (100 or less) [Figure 2] *1: The wiring used for analog input should adopt the connection cable or shielding cable of thermocouple temperature sensor J-type / K-type / R-type / S-type / T-type / E-type / N-type and should be separated from other power cable or wirings that may cause interference.
Temperature Explanation measurement module and cannot be changed via the instruction TO while connected to CPU series PLCs. Refer to Communication Format Setup in the appendix of the DVP programming manual for more details. The modules are numbered from 0 to 7 automatically by their When connected to distance from MPU.
Page 5
Attrib. Register name Explanation CH1~CH8. Average temp. measured at CH2 The average temperature measured at Average temp. measured at CH3 CH1~CH8 obtained from the average time settings in CR#10 ~ CR#17. Average temp. measured at CH4 Average temp. measured at CH5 Average temp.
Page 6
Error status Value b15 b14 b13 b12 b11 b10 b9 b8 b7 b1 b0 Abnormal digital range (H’4) of Ch1 Abnormal digital range (H’8) of Ch2 Abnormal digital range (H’10) of Ch3 Abnormal digital range (H’20) of Ch4 Abnormal digital range (H’40) of Ch5 Abnormal...
Page 16
………………………………………………………………… TÜRKÇE ………………………………………………………………… DELTA DVP PLC Serisini seçtiğiniz için teşekkürler. DVP08TC-H2 ürünü 8 adet 0~150mV voltaj giriş termokupl sıcaklık sensör (J-tipi, K-tipi, R-tipi, S-tipi, T-tipi, E-tipi, N-tipi) bilgisini alır ve bunları 24-bit dijital sinyallere dönüştürür. Ayrıca, DVP-EH2 MPU programı...
Sıcaklık Ölçüm Modülü Açıklama Cevap zamanı 200ms × kanal sayısı Dijital devreler ve analog devreler arası izolasyon. Kanallar arası izolasyon. 500VDC dijital devreler ve Ground arası Izolasyon 500VDC analog devreler ve Ground arası 500VDC analog devreler ve dijital devreler arası 500VDC 24VDC ve Ground arası...
Page 18
Özellik Register adı Açıklama O R/W CH3 ortalama adeti O R/W CH4 ortalama adeti O R/W CH5 ortalama adeti O R/W CH6 ortalama adeti O R/W CH7 ortalama adeti O R/W CH8 ortalama adeti K0 = Santigrad, K1 = Fahrenayt. O R/W Sıcaklık birimi Default =K0 CH1’de ölçülen Ortalama sıcaklık...
Page 19
Kalıcı CR’nin Kalıcı olabilmesi için RS-485 ile yazılması gerekir. Eğer MPU üzerinden TO/DTO komutları ile yazılırsa CR’ler kalıcı olmaz. (aşağıdaki tabloya bakınız) CR#37: Hata durumu Hata durumu Değer b15 b14 b13 b12 b11 b10 b9 b8 b7 Anormal besleme (H’1) Anormal modül (H’2) Ch1 Anormal...