Control Register - Delta DVP04TC-S Instruction Sheet

Temperature measurement module
Hide thumbs Also See for DVP04TC-S:

Advertisement

Available languages
  • EN

Available languages

There is isolation between channels.
Isolation method
500VDC between digital / analog circuits and Ground
(between digital and
500VDC between analog circuits and digital circuits
analog circuits)
500VDC between 24VDC and Ground
Digital data format
2's complement of 16-bit
Average function
Yes (CR#2 ~ CR#5)
Self diagnostic function
Yes
Supported, including ASCII/RTU mode. Default communication format:
9600, 7, E, 1, ASCII; refer to CR#32 for details on the communication
Communication mode
format. Note1: RS-485 cannot be used when connected to CPU series
(RS-485)
PLCs. Note2: Refer to Slim Type Special Module Communications in the
appendix E of the DVP programming manual for more details on RS-485
communication setups.
 Control Register
CR#
Address
Save
Register content
#0
H'4096
O
R
Model name
#1
H'4097
O
R/W
Thermocouple type
CR#1: Used to set the working mode of four channels. There are 5 modes (J-type, K-type, R-type,
S-type, and T-type) for each channel and can be set individually. For example, If you want to set
CH1~CH4 as following: CH1: mode 0 (b2 ~ b0=000), CH2: mode 1 (b5 ~ b3=001), CH3: mode 0 (b8 ~
b6=000) and CH4: mode 1 (b11 ~ b9=001), you should set CR#1 to H'0208. The higher bits (b12 ~ b15)
will be reserved and the default setting is H'0000.
#2
H'4098
O
R/W
CH1 average number
#3
H'4099
O
R/W
CH2 average number
#4
H'409A
O
R/W
CH3 average number
#5
H'409B
O
R/W
CH4 average number
CR#2 ~ CR#5: Please be noticed that when PLC sets average times via TO/DTO instructions, please
use rising-edge/falling-edge detection instruction (such as LDP and LDF) to get correct average times.
#6
H'409C
X
R
CH1 average degrees
#7
H'409D
X
R
CH2 average degrees
#8
H'409E
X
R
CH3 average degrees
#9
H'409F
X
R
CH4 average degrees
#10
X
R
CH1 average degrees
H'40A0
#11
H'40A1
X
R
CH2 average degrees
#12
X
R
CH3 average degrees
H'40A2
#13
X
R
CH4 average degrees
H'40A3
Present temp. of CH1
#14
X
R
H'40A4
Present temp. of CH2
#15
X
R
H'40A5
Present temp. of CH3
#16
X
R
H'40A6
Present temp. of CH4
#17
X
R
H'40A7
#19
X
R
Present temp. of CH1
H'40A9
Present temp. of CH2
#20
X
R
H'40AA
Present temp. of CH3
#21
X
R
H'40AB
Present temp. of CH4
#22
X
R
H'40AC
#24
H'40AE
O
R/W
CH1 OFFSET Value
#25
H'40AF
O
R/W
CH2 OFFSET Value
#26
H'40B0
O
R/W
CH3 OFFSET Value
#27
H'40B1
O
R/W
CH4 OFFSET Value
Description
Set up by the system:
DVP04TC-S model code=H'8B
b15~b12
b11~b9 b8~b6
b5~b3
b2~b0
Reserved
CH4
CH3
CH2
CH1
Example: Setting of CH1
1.
(b2, b1, b0) set to (0, 0, 0), use J-type.
2.
(b2, b1, b0) set to (0, 0, 1), use K-type.
3.
(b2, b1, b0) set to (0, 1, 0), use R-type.
4.
(b2, b1, b0) set to (0, 1, 1), use S-type.
5.
(b2, b1, b0) set to (1, 0, 0), use T-type.
Number piece of readings used for the
calculation of "average" temperature on
channels CH1 ~ CH4. Setting range:
For versions prior to V3.04: K1 ~ K4,095.
For versions after V3.05: K1 ~ K20.
Default setting is K10.
Average degrees for channels CH1 ~ CH4.
(Unit: 0.1°C).
Average degrees for channels CH1 ~ CH4.
(Unit: 0.1°F).
Present temperature of channels CH1 ~ CH4.
(Unit: 0.1°C).
Present temperature of channels CH1 ~ CH2.
(Unit: 0.1°F).
Present temperature of channels CH3 ~ CH4.
(Unit: 0.1°F).
Adjust offset value of channels CH1 ~ CH4.
The range is -1,000 ~ +1,000 and default
setting is K0.
(Unit: 0.1°C).
- 3 -