Other Specifications; Control Register - Delta DVP Series Instruction Sheet

Temperature measurement module
Hide thumbs Also See for DVP Series:

Advertisement

Available languages
  • EN

Available languages

Temperature
measurement module
When connected to
DVP-PLC MPU in series
 Other Specifications
Max. rated power
consumption
Operation/storage
Vibration/shock
immunity
 Control Register
CR#
Attrib.
#0
O
R
#1
O
R
#2
O R/W CH1 thermocouple type
#3
O R/W CH2 thermocouple type
#4
O R/W CH3 thermocouple type
#5
O R/W CH4 thermocouple type
#6
O R/W CH5 thermocouple type
#7
O R/W CH6 thermocouple type
#8
O R/W CH7 thermocouple type
#9
O R/W CH8 thermocouple type
#10
O R/W CH1 average time
#11
O R/W CH2 average time
#12
O R/W CH3 average time
#13
O R/W CH4 average time
#14
O R/W CH5 average time
#15
O R/W CH6 average time
#16
O R/W CH7 average time
#17
O R/W CH8 average time
#18
O R/W Temperature unit
#19
X
R
and cannot be changed via the instruction TO while connected to
CPU series PLCs. Refer to Communication Format Setup in the
appendix of the DVP programming manual for more details.
The modules are numbered from 0 to 7 automatically by their
distance from MPU. No. 0 is the closest to MPU and No. 7 is the
furthest. Maximum 8 modules are allowed to connect to MPU and
will not occupy any digital I/O points.
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by
external power.
1. Operation: -10°C~ 60°C (Temperature), 5 ~ 95% (Humidity), pollution
degree 2
2. Storage: -25°C~ 70°C (Temperature), 5 ~ 95%(Humidity)
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC
68-2-27 (TEST Ea)
Register name
Model name
Firmware version
Average temp. measured at CH1
Explanation
Power supply
Environment
Set up by the system.
DVP08TC-H2 model code = H'6804
User can read the model name from the
program and see if the extension
module exists.
Displaying the current firmware version
in hex; e.g. version 1.01 is indicated as
H'0101
There are 10 setting options for the
thermocouple type, shown in
hexadecimal digits:
H0000: J-type; H0001: K-type;
H0002: R-type; H0003: S-type;
H0004: T-type; H0005: E-type;
H0006: N-type; H0007: 0~150mV;
H0008: ±150mV; HFFFF: channel
closed; Default value: H'0000;
For options not listed above are
reserved for system use.
Range of settings in CH1 ~ CH8:
K1 ~ K100. Default =K10.
K0 = centigrade, K1 = Fahrenheit.
Default =K0
Average temperature measured at
- 3 -
Explanation