Delta DVP04AD-H2 Instruction Sheet

Delta DVP04AD-H2 Instruction Sheet

Analog input module

Advertisement

Quick Links

http://www.delta.com.tw/industrialautomation/
Analog Input Module
Instruction Sheet
Warning
Please read this instruction carefully before use.
Switch off the power before wiring.
DVP04AD-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of
airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance
staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case
danger and damage on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may
occur. Check all the wiring again before switching on the power.
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1
minute after the power is switched off.
Make sure the groud terminal
is correctly grounded in order to prevent electromagnetic
interference.
Introduction
1.1 Model Explanation & Peripherals
Thank you for choosing Delta DVP series. DVP04AD-H2 is able to receive 4 points of analog input signals
(voltage or current) and convert them into 14-bit digital signals. Besides, through FROM/TO instructions in
DVP-EH2 MPU program, DVP04AD-H2 is able to read and write the data in the module. There are 49 16-bit
control registers (CR) in DVP04AD-H2.
The user can select voltage or current output by wiring. Range of voltage output: ±10VDC (resolution: 1.25mV).
Range of current output: ±20mA (resolution: 5μA).
Nameplate Explanation
D e l t a P L C m o d e l n a m e
P o w e r i n p u t s p e c i f i c a t i o n
A n a l o g I / O m o d u l e s p e c i f i c a t i o n
B a r c o d e , s e r i a l N o . , V e r s i o n
VX.XXXX
Model/Serial No. Explanation
DVP series
H: For EH series MPU
H2: For EH2 series MPU
Points (input + output)
Module type
AD: Analog input
XA: Mixed analog I/O
DA: Analog output
HC: High-speed counter input
PT: Temperature measurement (PT-100)
PU: Single-axis position control
TC: Temperature measurement (thermocouple)
1.2 Product Profile (Indicators, Terminal Block, I/O Terminals)
Unit: mm
1
6
DIN rail (35mm)
Terminals
2
Connection port for extension modules
7
Mounting hole
3
8
Model name
I/O terminals
4
POWER, ERROR, A/D indicator
9
Mounting port for extension modules
5
DIN rail clip
2006-12-12
1.3 External Wiring
5011651500-A2E0
*1. When performing analog input, please isolate other power wirings.
*2. If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring
to 0.1 ~ 0.47μF 25V capacitor.
*3. Please connect the
system contact or connect it to the cover of power distribution cabinet.
NOTE: DO NOT wire empty terminals
Specifications
2.1.
Functions
Analog/Digital (4A/D) Module
Power supply voltage
Analog input channel
Range of analog input
Range of digital
conversion
24 Vdc 2.5W
Resolution
-1 0V ~ + 10V or -20mA ~ +20mA
1.25 mV or 5
A
Input impedance
04 AD -H2 0T6 50 000 1
Overall accuracy
MADE I N XXXXX X
Responding time
Isolation
Production No.
Production week
Range of absolute input
Production year (2006)
Digital data format
Production plant (Taoyuan)
Version No.
Average function
Model name
Self-diagnosis
Communication mode
(RS-485)
When connected to
DVP-PLC MPU in series
2.2.
Others
Max. rated power
consumption
8
Operation/storage
Vibration/shock
immunity
Voltage input
-10V~+10V
CH1
100K
V+
250
I+
*5
100K
COM
FG
Shielding cable*1
AG
Current input
CH4
100K
-20mA~+20mA
V+
*2
250
I+
100K
COM
FG
Shielding cable*1
AG
*3
Terminal of
power module
DC/DC
24+
*4
24-
Converter
System grounding
Earth
(100
or less)
terminal on both the power modules and DVP04AD-H2 to the system earth point and ground the
Voltage input
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
4 channels/module
±10V
±20mA
±8,000
±4,000
14 bits (1
= 2.5mV)
13 bits (1
= 5μA)
LSB
LSB
0.5Ω or lower
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
3ms × the number of channels
Internal circuit and analog output terminals are isolated by optical coupler.
No isolation among analog channels.
±15V
±32mA
13 significant bits out of 16 bits are available; in 2's complement
Yes. Available for setting up in CR#2 ~ CR#5; range: K1 ~ K20.
Upper and lower bound detection/channel
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU.
The modules are numbered from 0 to 7 automatically by their distance from MPU.
No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed
to connect to MPU and will not occupy any digital I/O points.
Power Supply
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)., 2.5W supplied by external power
Environment
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity)
International standards: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC
68-2-27 (TEST Ea)
Control Registers
DVP04AD-H2
RS-485
CR#
Latched
Register content
Parameter
CH1
address
#0
H'4000 ○
R
Model name
#1
H'4001 ○ R/W Input mode setting
CH4
#2
H'4002 ○ R/W CH1 average time
#3
H'4003 ○ R/W CH2 average time
#4
H'4004 ○ R/W CH3 average time
#5
H'4005 ○ R/W CH4 average time
#6
H'4006
X
R
CH1 input average
#7
H'4007
X
R
CH2 input average
+15V
#8
H'4008
X
R
CH3 input average
AG
#9
H'4009
X
R
CH4 input average
-15V
#10~ #11
CH1 input present
#12
H'400C X
R
value
CH2 input present
#13
H'400D X
R
value
CH3 input present
#14
H'400E X
R
value
CH4 input present
#15
H'400F X
R
value
#16~ #17
Adjusted OFFSET
#18
H'4012 ○ R/W
value of CH1
Adjusted OFFSET
#19
H'4013 ○ R/W
value of CH2
Adjusted OFFSET
#20
H'4014 ○ R/W
value of CH3
Adjusted OFFSET
#21
H'4015 ○ R/W
value of CH4
#22~ #23
Adjusted GAIN value of
#24
H'4018 ○ R/W
Current input
CH1
Adjusted GAIN value of
#25
H'4019 ○ R/W
CH2
Adjusted GAIN value of
#26
H'401A ○ R/W
CH3
Adjusted GAIN value of
#27
H'401B ○ R/W
CH4
#28~ #29
#30
H'401E X
R
Error status
Communication
#31
H'401F ○ R/W
address setting
Communication speed
#32
H'4020 ○ R/W
(baud rate) setting
Returning to default
#33
H'4021 ○ R/W
setting; OFFSET/GAIN
tuning authorization
#34
H'4022 ○
R
Firmware version
#35 ~ #48
Symbols
○: latched (when written in through RS-485 communication)
: non-latched
R: Able to read data by FROM instruction or RS-485 communication
W: Able to write data by TO instruction or RS-485 communication
LSB (Least Significant Bit): For voltage input 1
For current input 1
Explanations:
1. CR#0: Model name. The user can read the model name from the program and see if the extension module
exists.
2. CR#1: The working mode of the two channels in the analog output module. There are 4 modes for each channel
which can be set up separately. For example, if the user needs to set up CH1: mode 2 (b2 ~ b0 = 010) and CH2:
mode 1 (b5 ~ b3 = 001), CR#1 has to be set as H000A and the higher bits (b12 ~ b15) have to be reserved.
Default value = H'0000.
Description
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
Set up by the system. DVP04AD-H2 model code = H'6400
reserved
CH4
CH3
CH2
CH1
Input mode: Default = H'0000
Mode 0: Voltage input (-10V ~ +10V)
Mode 1: Voltage input (-6V ~ +10V)
Mode 2: Current input (-12mA ~ +20mA)
Mode 3: Current input (-20mA ~ +20mA)
Range of settings in CH1 ~ CH4: K1 ~ K20. Default = K10.
Average of input signals at CH1 ~ CH4
Reserved
Present value of input signals at CH1 ~ CH4
Reserved
OFFSET settings at CH1 ~ CH4. Default = K0; Unit: LSB
When voltage input, range: K-4,000 ~ K4,000
When current input, range: K-4,000 ~ K4,000
Reserved
GAIN settings at CH1 ~ CH4. Default = K4,000; Unit: LSB
When voltage input, range: K-3,200 ~ K16,000
When current input, range: K-3,200 ~ K10,400
Reserved
Register for storing all error status. See the table of error status for more
information.
For setting RS-485 communication address. Range: 01 ~ 255. Default = K1
For setting up communication speed:
4,800/9,600/19,200/38,400/57,600/115,200bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default = H'0002
b0: 4,800bps
b1: 9,600bps (default)
b2: 19,200bps b3: 38,400bps
b4: 57,600bps b5: 115,200bps
b6 ~ b13: reserved
b14: High/low bit exchange of CRC checksum (only valid in RTU mode)
b15: Switch between ASCII/RTU mode; 0 = ASCII mode (default)
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
reserved
CH4
CH3
CH2
CH1
Default = H'0000. Take the setting of CH1 for example:
1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET) and CR#24
(GAIN) of CH1. When b0 = 1, the user is not allowed to tune CR#18
(OFFSET) and CR#24 (GAIN) of CH1.
2. b1 represents whether the OFFSET/GAIN tuning registers are latched. b1
= 0 (default, latched); b1 = 1 (non-latched)
3. When b2 = 1, all settings will return to default values.
Displaying the current firmware version In hex; e.g. version 1.0A is indicated as
H'010A.
For system use
= 10V/8,000 = 1.25mV。
LSB
= 20mA/4,000 = 5μA。
LSB
b0
b0

Advertisement

loading

Summary of Contents for Delta DVP04AD-H2

  • Page 1 (voltage or current) and convert them into 14-bit digital signals. Besides, through FROM/TO instructions in value of CH4 2.1. Functions DVP-EH2 MPU program, DVP04AD-H2 is able to read and write the data in the module. There are 49 16-bit #22~ #23 Reserved control registers (CR) in DVP04AD-H2.