Download Print this page

Functions Specifications; Control Register - Delta DVP04PT-E2 Instruction Sheet

Temperature measurement module

Advertisement

Available languages

Available languages

Operation/storage
Vibration/shock
immunity
Series connection to
DVP-PLC MPU
 Functions Specifications
DVP04/06PT-E2
Analog input
channel
Digital data format
Response time
Overall accuracy
Applicable sensor
type
Input temperature
range
Range of digital
conversion
Resolution
Average function
Self-diagnosis
Isolation
*1: The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be
Fahrenheit, the second decimal place would not be shown.
 Control Register
04P 06P Attrib.
#0
#0
O
R
#1
#1
O
R
DVP04/06PT-E2
Operation: 0°C~55°C (temp.), 5~95% (humidity), Pollution degree2
Storage: -25°C~70°C (temp.), 5~95% (humidity)
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
The modules are numbered from 0 to 7 automatically by their
distance from MPU. No.0 is the closest to MPU and No.7 is the
furthest. Maximum 8 modules are allowed to connect to MPU and
will not occupy any digital I/O points.
Celsius (°C)
4/6 channels
2's complement of 16 bits
200ms / each channel
±0.3% when in full scale (25°C, 77°F)
±0.6% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
04PT:3-Wire Pt100 (DIN 43760-1980 JIS C1604-1989, 100Ω 3850 PPM/°C);
Pt1000 (DIN EN60751, 1 kΩ 3850 PPM/°C); Ni100 / Ni1000(DIN 43760); 0 ~
300Ω/0 ~ 3000Ω input impedance
06PT:3- Wire Pt100 (DIN 43760-1980 JIS C1604-1989, 100Ω 3850 PPM/°C);
Pt1000 (DIN EN60751, 1 kΩ 3850 PPM/°C) ; Ni100 / Ni1000(DIN 43760);
Cu50;Cu100;JPt100 (JIS C1604-1989);LG-Ni1000;0 ~ 300Ω/0 ~ 3000Ω input
impedance
Pt100: -180°C ~ 800°C
Ni100: -80°C ~ 170°C
Pt1000: -180°C ~ 800°C
Ni1000: -80°C ~ 170°C
JPt100: -180°C ~ 500°C
Cu50: -50°C ~ 150°C
Cu100: -50°C ~ 150°C
LG-Ni1000: -50°C ~ 180°C
Pt100: K-1,800 ~ K8,000
Ni100: K-800 ~ K1,700
Pt1000: K-1,800 ~ K8,000
Ni1000: K-800 ~ K1,700
JPt100: K-1,800 ~ K5,000
Cu50: K-500 ~ K1,500
Cu100: K-500 ~ K1,500
LG-Ni1000: K-500 ~ K1,800
0.1°C
Range: K1 ~ K100.
Upper and lower bound detection in all channels
Optical coupler isolation between digital circuits and analog circuits. No isolation
among analog channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Register content
Model name
Firmware version
Fahrenheit (°F)
Pt100: -180°C ~ 800°C
Ni100: -80°C ~ 170°C
Pt1000: -180°C ~ 800°C
Ni1000: -80°C ~ 170°C
JPt100: -180°C ~ 500°C
Cu50: -50°C ~ 150°C
Cu100: -50°C ~ 150°C
LG-Ni1000: -50°C ~ 180°C
Pt100: K-1,800 ~ K8,000
Ni100: K-800 ~ K1,700
Pt1000: K-1,800 ~ K8,000
Ni1000: K-800 ~ K1,700
JPt100: K-1,800 ~ K5,000
Cu50: K-500 ~ K1,500
Cu100: K-500 ~ K1,500
LG-Ni1000: K-500 ~ K1,800
*1
0.18°F
DVP04PT-E2 model code = H'0082
DVP06PT-E2 model code = H'00C2
Display the current firmware version in hex.
- 3 -
Input
Impedance
0 ~ 300Ω
0 ~ 3000Ω
K0 ~ K3,000
K0 ~ K30,000
0.1Ω
Description

Advertisement

loading

This manual is also suitable for:

Dvp06pt-e2