Mounting rules
Vertical rack mounting
Please observe the following rules for vertical rack mounting:
• A maximum of 10 units (2 blocks - 5 units) can be mounted within one rack. In
that case a heat baffle should be placed in the middle of the rack as shown in the
figures below.
• The minimum distance between two blocks must be 400 mm [15.748"] if no heat
baffle is used (measured from top of the lower block to bottom of the upper block).
Figure A-2 Vertical mounting (AM/AMS, DC)
...................................................................................................................................................................................................................................
365-312-802R7.2
Issue 4, June 2007
Rack
bar
bar
Heat Baffle
bar
bar
Alcatel-Lucent - Proprietary
See notice on first page
AM/AMS units (DC powered)
A-3