Service and maintenance
9.2 Error messages
"ER"
XML/
Bloc (hex)
LED
LED
(hex)
2 Hz
0x63
0xE6FE03
--
0x64
0xE6FE04
--
0x65
0xE6FE05
238
Error description
A parameter of an XML command has an invalid value or the parameter assignment of
•
the communications module or the reader was incorrect.
Possible causes / action to be taken:
–
Check the parameters in the Ident profile.
–
Check the relevant XML command.
–
Check the parameter assignment in HW Config / STEP 7 (TIA Portal).
–
The "WRITE-CONFIG" command has incorrect parameter settings.
–
After a startup, the reader or communications module has still not received an INIT".
The parameter assignment of the reader or communications module on
•
PROFIBUS/PROFINET was incorrect and the command cannot be executed.
Possible causes / action to be taken:
–
Length of the input/output areas is too small for the cyclic I/O word.
–
Check whether you have used the correct GSD file.
–
The command (e.g. "READ") applied to the user data with too great a length.
Error when processing the command.
•
Possible causes / action to be taken:
–
Bad data in the "AdvancedCmd" or "IID_CMD_STRUCT" (e.g. "WRITE" command
with length = 0).
Check "AdvancedCmd" or "IID_CMD_STRUCT" and execute an "INIT".
–
The hardware of the reader/communications module is defective. The reader or
communications module receives bad data with an "INIT".
–
The AB byte does not match the user data length.
The wrong reset block was selected.
•
Possible causes / action to be taken:
–
Regardless of the selected reader system, use the "Reset_Reader" function block.
Presence error
A transponder has passed through the transmission window of a reader without being pro-
cessed.
This error message is not reported immediately. Instead, the reader or communications
•
module waits for the next write / read command. This command is replied to immediate-
ly with this error and the write/read command is not executed. The next command is ex-
ecuted normally again by the reader/communications module.
You can reset this error status using an "INIT".
•
Bit 2 is set in the "OPT1" parameter and there is no transponder in the transmission
•
window.
An error has occurred that makes a Reset_Reader ("WRITE-CONFIG" with "Config = 3")
necessary.
Possible causes / action to be taken:
The "WRITE-CONFIG" command is incorrect.
•
After eliminating the error, execute an "INIT".
•
Check the "IID_HW_CONNECT" parameter.
•
SIMATIC RF650R/RF680R/RF685R
Configuration Manual, 10/2015, C79000-G8976-C386-03