Interface to the SIMATIC controller
7.7 Programming the Ident profile
Figure 7-23
Note
End the Repeat command with "INIT" or "SRESET"
End the Repeat command using the input parameters "INIT" or "SRESET" if it is not known
how many transponders were still processed after resetting the "RPTCMD" input parameter.
Normally, an "SRESET" is performed significantly faster because not reset routine is run
through.
Ending the Repeat command with "INIT":
1. Reset the "RPTCMD" input parameter and set the "INIT" input parameter.
If "RPTCMD" is not reset, the Repeat command is activated again on the reader. This
response triggers an error message because there is no command.
2. The reader resets the "RPTACT" output parameter due to the "INIT" input parameter.
136
End the Repeat command by resetting "RPTCMD" (the last command remains pending)
SIMATIC RF650R/RF680R/RF685R
Configuration Manual, 10/2015, C79000-G8976-C386-03