6
HIGH-SPEED COUNTER MODULE REPLACEMENT

6.2.3 I/O signal comparison

Sequence programs need to be changed because the I/O signal assignment differs.
For details of the I/O signals and sequence programs, refer to the MELSEC-L High-Speed Counter
Module User's Manual.
When the built-in I/O functions of the LCPU are used, the special relay is used. For details, refer to the
MELSEC-L CPU Module User's Manual (Built-in I/O Function).
A1SD61
Device
Signal name
No.
X0
Watchdog timer error flag
CH1 limit switch output status
X1
flag
CH2 limit switch output status
X2
flag
CH3 limit switch output status
X3
flag
CH4 limit switch output status
X4
flag
CH5 limit switch output status
X5
flag
CH6 limit switch output status
X6
flag
CH7 limit switch output status
X7
flag
CH8 limit switch output status
X8
flag
Limit switch output enable
X9
flag
External preset command
XA
detection flag
XB
Error flag
Fuse/external power cutoff
XC
detection flag
Sampling/periodic counter
XD
flag
XE
XF
X10
X11
X12
X13
X14
X15
Use prohibited
X16
X17
X18
X19
X1A
X1B
X1C
X1D
X1E
X1F
Device
Signal name
No.
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Use prohibited
Y8
Y9
YA
YB
YC
YD
YE
YF
Y10
Count enable command
Y11
Decrement count command
Y12
Preset command
Y13
Ring counter command
Counter function selection
Y14
start command
Y15
Limit switch output command
External preset command
Y16
detection reset command
Y17
Error reset command
Y18
Y19
Y1A
Y1B
Use prohibited
Y1C
Y1D
Y1E
Y1F
L62D
Device
Signal name
No.
X0
Module READY
CH1 Counter value large
X1
(point No.1)
CH1 Counter value
X2
coincidence (point No.1)
CH1 Counter value small
X3
(point No.1)
CH1 External preset request
X4
detection
CH1 Counter value large
X5
(point No.2)
CH1 Counter value
X6
coincidence (point No.2)
CH1 Counter value small
X7
(point No.2)
CH2 Counter value large
X8
(point No.1)
CH2 Counter value
X9
coincidence (point No.1)
CH2 Counter value small
XA
(point No.1)
CH2 External preset request
XB
detection
CH2 Counter value large
XC
(point No.2)
CH2 Counter value
XD
coincidence (point No.2)
CH2 Counter value small
XE
(point No.2)
XF
Use prohibited
Device
Signal name
No.
CH1 Coincidence signal No.1
Y0
reset command
Y1
CH1 Preset command
CH1 Coincidence signal
Y2
enable command
Y3
CH1 Down count command
Y4
CH1 Count enable command
CH1 External preset
Y5
detection reset command
CH1 Counter function
Y6
selection start command
CH1 Coincidence signal No.2
Y7
reset command
CH2 Coincidence signal No.1
Y8
reset command
Y9
CH2 Preset command
CH2 Coincidence signal
YA
enable command
YB
CH2 Down count command
YC
CH2 Count enable command
CH2 External preset
YD
detection reset command
CH2 Counter function
YE
selection start command
CH2 Coincidence signal No.2
YF
reset command
6