ANALOG I/O MODULE REPLACEMENT
4

4.1 List of Analog I/O Module Alternative Models for Replacement

AnS/QnAS series
Product
Analog I/O module
4
- 1
ANALOG I/O MODULE
4
REPLACEMENT
Model
A1S63ADA
A1S66ADA
Transition to L series
Model
1) External wiring: Cable size is changed.
2) Number of slots: Not changed
3) Program: The number of occupied I/O points, I/O
signals, and buffer memory addresses are changed.
L60AD2DA2
4) Performance specifications: An external power
supply (24VDC) is required.
5) Functional specifications: Simple loop control
(function expression) function available  Not
available
1) External wiring: Cable size is changed.
2) Number of slots: Not changed
3) Program: The number of occupied I/O points, I/O
L60AD2DA2
signals, and buffer memory addresses are changed.
4) Performance specifications: Analog input 4CH 
2CH
5) Functional specifications: Not changed
Remarks (Restrictions)