Functional Comparison - Mitsubishi Electric MELSEC L Series Manual

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

4
ANALOG I/O MODULE REPLACEMENT

4.3.2 Functional comparison

(1) A/D conversion functions
Item
Sets whether to enable or disable A/D conversion for each
A/D conversion enable/disable
channel. By disabling the conversion for the channels that are
function
not used, the sampling time can be shortened.
Performs the A/D conversion for analog input values
Sampling processing
successively for each channel, and outputs digital output values
upon each conversion.
For each channel, averages A/D conversion values by the
Time average
amount of time, and outputs the average value as a digital
value.
For each channel, averages A/D conversion values by the
Averaging
Count average
number of times, and outputs the average value as a digital
processing
value.
For each channel, averages A/D conversion values by the
Moving average
number of times on a moving of each sampling processing, and
outputs the average value as a digital value.
Range switching function
Sets the input range to be used.
Extends the input range. By combining this function with the
Input range extended function
input signal error detection function, simple disconnection
detection can be executed.
Maximum value/minimum value
Stores the maximum and minimum values of the digital output
hold function
values in the module.
Input signal error detection
Detects the analog input value which exceeds the setting range.
function
Scale-converts the digital output value to the set range of the A/
D conversion scaling upper limit value and A/D conversion
Scaling function
scaling lower limit value. This omits the programming of the
scale conversion.
Logs the digital output value or scaling value (digital operation
Logging function
value). The data of 10000 points can be logged for each
channel.
(2) D/A conversion functions
Item
Sets whether to enable or disable D/A conversion for each
D/A conversion enable/disable
channel.
function
With the L60AD2DA2, disabling the D/A conversion for an
unused channel reduces the conversion cycles.
Sets whether to output the D/A conversion value or 0V/0mA for
each channel.
The conversion speed is constant, regardless of the output
enable/disable status.
D/A output enable/disable
function
Sets whether to output the D/A conversion value or the offset
value for each channel.
The conversion speed is constant, regardless of the output
enable/disable status.
Range switching function
Sets the output range to be used.
Sets the status of analog output values (HOLD or CLEAR),
Analog output HOLD/CLEAR
according to the CPU module operating status (RUN, STOP, or
function
stop error).
Outputs the D/A converted analog values when CH. Output
Analog output test when CPU
enable/disable flag is forcibly turned on while the CPU module is
module is in STOP status
in the STOP status.
4
- 25
Description
Description
: Available, –: Not available
A1S66ADA L60AD2DA2 Precautions for replacement
To use the same digital output
value that is used for the
A1S66ADA, set the scaling
upper and lower limit values
that match the resolution of the
A1S66ADA using the scaling
function.
: Available, –: Not available
A1S66ADA L60AD2DA2 Precautions for replacement
Output varies when D/A output
is disabled.