Functional Comparison - Mitsubishi Electric MELSEC L Series Manual

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

2
ANALOG INPUT MODULE REPLACEMENT

2.4.2 Functional comparison

Item
Sets whether to enable or disable the A/D conversion. By
A/D conversion enable/ disable
disabling the conversion for the channels that are not used, the
function
sampling time can be shortened.
Performs the A/D conversion for analog input values
Sampling processing
successively for each channel, and outputs digital output values
upon each conversion.
For each channel, averages A/D conversion values by the
Time average
amount of time, and outputs the average value as a digital
value.
For each channel, averages A/D conversion values by the
Averaging
Count average
number of times, and outputs the average value as a digital
processing
value.
For each channel, averages A/D conversion values by the
Moving average
number of times on a moving of each sampling processing, and
outputs the average value as a digital value.
Range switching function
Sets the input range to be used.
Offset/gain setting function
Compensates for errors in digital output values.
Extends the input range. By combining this function with the
Input range extended mode
input signal error detection function, simple disconnection
function
detection can be executed.
Maximum value/minimum value
Stores the maximum and minimum values of the digital output
hold function
values in the module.
Input signal error detection
Detects the analog input value which exceeds the setting range.
function
Extends the detection method of the input signal error detection
Input signal error detection
function. Use this function to detect the input signal error only in
extension function
the lower limit or upper limit, or to execute the disconnection
detection.
Warning output function
Outputs an alarm when a digital output value is within the range
(process alarm)
set in advance.
Sets the resolution according to the application. The resolution
Resolution mode
mode setting is applicable to all channels.
Scale-converts the output digital value to the set range of the
Scaling function
scaling upper limit value and scaling lower limit value. This omits
the programming of the scale conversion.
Adds the set shifting amount of the conversion value to the
scaling value (digital operation value) and stores the value in the
Shift function
buffer memory. Fine adjustment can be performed easily when
the system starts.
Sets the maximum value of the scaling value (digital operation
Digital clipping function
value) to 20000 and the minimum value to 0 or -20000 when the
input voltage or current exceeds the input range.
Subtracts the difference conversion reference value from the
Difference conversion function
scaling value (digital operation value) and stores the acquired
value in the buffer memory.
Logs the digital output value or scaling value (digital operation
Logging function
value). The data of 10000 points can be logged for each
channel.
Stores the errors and alarms occurred in the A/D converter
Error log function
module to the buffer memory as a history. Up to 16 errors and
alarms can be stored.
Collects the errors and alarms occurred in the A/D converter
Module error collection function
module and stores them in the CPU module.
Clears the error from the system monitor window of the
Error clear function
programming tool.
Saving and restoring offset/gain
Saves and restores the offset/gain values in the user setting
values
range.
2
- 30
Description
*1
: Compatible,
: Partial change required, ×: Incompatible
L60ADVL8
A1S68AD
Precautions for replacement
L60ADIL8
The setting range of average time
and count differs.
Refer to the MELSEC-L Analog-
Digital Converter Module User's
Manual, and check the
specifications.
By setting the same scaling
upper limit value and scaling
lower limit value as the resolution
of A1S68AD, the same digital
output values as A1S68AD can
be used.
*2
This function can be used on GX
Works2.