4
ANALOG I/O MODULE REPLACEMENT
-10 to 10VDC (Input resistance value: 1M)
0 to 20mA (Input resistance value: 250)
16-bit signed binary (-16384 to 16383,
When the scaling function is used: -32768 to 32767)
Analog input range
0 to 10V
-10 to 10V
Voltage
(Extended mode)
User range settings
(voltage)
0 to 20mA
4 to 20mA
4 to 20mA
Current
(Extended mode)
User range settings
(current)
Analog input range
0 to 10V
-10 to 10V
0 to 5V
Voltage
1 to 5V
1 to 5V
(Extended mode)
0 to 20mA
4 to 20mA
Current
4 to 20mA
(Extended mode)
L60AD2DA2
2 channels/module
Digital output value
0 to 16000
0 to 5V
0 to 12000
1 to 5V
-16000 to 16000
1 to 5V
-3000 to 13500
-12000 to 12000
0 to 12000
-3000 to 13500
-12000 to 12000
Ambient temperature
25±5°C
Within ±0.2%
(±32 digit)
Within ±0.2%
(±24 digit)
80µs/channel
Voltage: ±15V
Current: 30mA
: Compatible,
Compatibility
Resolution
625µV
416µV
333µV
625µV
333µV
321µV
1666nA
1333nA
1333nA
1287nA
0 to 55°C
Within ±0.3%
(±48 digit)
Within ±0.3%
(±36 digit)
: Partial change required, ×: Incompatible
Precautions for replacement
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)
The conversion speed of
L60AD2DAQ2 is faster than
A1S63ADA. Therefore, noise
which were not imported to
A1S63ADA can be imported as
analog signals. In this case, use
the averaging processing function
to remove the effect of noise.