Mitsubishi Electric MELSEC L Series Manual page 35

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

2
ANALOG INPUT MODULE REPLACEMENT
(Input resistance value: 1M)
(Input resistance value: 250)
16-bit signed binary
(-20480 to 20479, when the scaling function is used: -32768 to 32767)
Analog input range
0 to 10V
0 to 5V
1 to 5V
Voltage
-10 to 10V
1 to 5V (Extended mode)
User range setting
0 to 20mA
4 to 20mA
Current
4 to 20mA
(Extended mode)
User range setting
Ambient temperature within 25±5°C: ±0.1% (±20 digit)
Ambient temperature within 0 to 55°C: ±0.2% (±40 digit)
High speed: 20µs/channel (default)
Medium speed: 80µs/channel
Low speed: 1ms/channel
4 channels/module
Between the I/O terminal and programmable controller power supply: Photocoupler
Between channels: Not insulated
Between the I/O terminal and programmable controller power supply: 500VACrms, for 1
Between the I/O terminal and programmable controller power supply: 500VDC, 10M or
(I/O assignment: intelligent 16 points)
18-point terminal block
R1.25-3 (Solderless terminals with an insulation sleeve cannot be used.)
L60AD4
-10 to 10VDC
0 to 20mA
Digital output value
0 to 20000
-20000 to 20000
-5000 to 22500
-20000 to 20000
0 to 20000
-5000 to 22500
-20000 to 20000
Voltage: ±15V
Current: ±30mA
Up to 50000 times
minute
higher
16 points
2
0.3 to 0.75mm
0.52A
0.19kg
: Compatible,
Compatibility
Resolution
500µV
250µV
200µV
500µV
200µV
307µV
1000nA
800nA
800nA
1230nA
×
×
×
: Partial change required, ×: Incompatible
Precautions for replacement
Since the resolution differs between AnS series
and L series modules, it needs to be matched
using a sequence program, user range settings,
or the scaling function (refer to Appendix 3).
The conversion speed of L60AD4 is faster than
A1S68AD. Therefore, noise which were not
imported to A1S68AD can be imported as analog
signals. In this case, use the averaging
processing function to remove the effect of noise.
Consider of replacing with several L60AD4
modules.
The number of occupied I/O points is changed to
16 points.
Wiring needs to be changed.
Recalculation of internal current consumption
(5VDC) is required.
2