ANALOG INPUT MODULE REPLACEMENT
Item
Clears the error from the system monitor window of the
Error clear function
programming tool.
Saving and restoring offset/gain
Saves and restores the offset/gain values in the user setting
values
range.
*1
For the A1S68AD, the resolution is 1/4000 (fixed).
For the L60AD4, the resolution is 1/20000 (fixed). To use the same digital value that is used for the A1S68AD, set the
scaling upper and lower limit values that match the resolution of the A1S68AD using the scaling function.
Description
: Supported,
A1S68AD
L60AD4
Precautions for replacement
This function can be used on GX
–
Works2.
–
–
: Not supported
2
- 19