2
ANALOG INPUT MODULE REPLACEMENT
-10 to 10VDC (Input resistance value: 1M)
0 to 20mA (Input resistance value: 250)
16-bit signed binary (-20480 to 20479,
When the scaling function is used: -32768 to 32767)
Analog input range
0 to 10V
0 to 5V
1 to 5V
Voltage
-10 to 10V
1 to 5V (Extended mode)
User range setting
0 to 20mA
4 to 20mA
Current
4 to 20mA (Extended mode)
User range setting
Ambient temperature within 25±5°C: ±0.1% (±20 digit)
Ambient temperature within 0 to 55°C: ±0.2% (±40 digit)
L60AD4
Digital output
Resolution
500µV
0 to 20000
250µV
200µV
-20000 to 20000
500µV
-5000 to 22500
200µV
-20000 to 20000
307µV
1000nA
0 to 20000
800nA
-5000 to 22500
800nA
-20000 to 20000
1230nA
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Precautions for replacement
Since the resolution differs between AnS
series and L series modules, it needs to be
matched using a sequence program, user
range settings, or the scaling function (refer
to Appendix 3).