4
ANALOG I/O MODULE REPLACEMENT
When the scaling function is used: -32768 to 32767)
Analog input range
0 to 10V
0 to 5V
1 to 5V
Voltage
-10 to 10V
1 to 5V
(Extended mode)
User range settings
0 to 20mA
4 to 20mA
Current
4 to 20mA
(Extended mode)
User range settings
Analog input range
0 to 10V
-10 to 10V
0 to 5V
Voltage
1 to 5V
1 to 5V
(Extended mode)
0 to 20mA
4 to 20mA
Current
4 to 20mA
(Extended mode)
L60AD2DA2
2 channels/module
-10 to 10VDC
(Input resistance value: 1M)
0 to 20mA
(Input resistance value: 250)
16-bit signed binary
(-16384 to 16383,
Digital output value
0 to 16000
0 to 12000
-16000 to 16000
-3000 to 13500
-12000 to 12000
0 to 12000
-3000 to 13500
-12000 to 12000
Ambient temperature
25±5°C
Within ±0.2%
(±32 digit)
Within ±0.2%
(±24 digit)
80µs/channel
Voltage: ±15V
Current: 30mA
: Compatible,
Compatibility
Resolution
625µV
416µV
333µV
625µV
333µV
321µV
1666nA
1333nA
1333nA
1287nA
0±55°C
Within ±0.3%
(±48 digit)
Within ±0.3%
(±36 digit)
: Partial change required, ×: Incompatible
Precautions for replacement
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)