Appendix 3 How to Change Resolution After Analog I/O Module is
Replaced
This section describes how to change the resolution of an analog I/O module after the module is
replaced from AnS series to L series.

Appendix 3.1 Resolution

The following table lists a example of the resolutions for the AnS series and L series analog I/O
modules.
Each AnS series analog I/O module has different resolution. Please check the resolution of the
module in this handbook or user
If the resolution differs between AnS series and L series modules, it needs to be matched by a user (by
creating a sequence program or changing user range settings).
Resolution of AnS series analog I/O module
A1S64AD
A1S62DA
A1S63ADA
*1
Adjust the resolution using the scaling function. (Refer to Appendix 3.2.)
*2
Change the resolution in a sequence program. (Refer to Appendix 3.2.)

Appendix 3.2 Using the scaling function of an analog I/O module

By using the scaling function of the L series analog I/O module, a resolution can be changed.
(1) Example of setting intelligent function module parameters
Parameters can easily be set by using the intelligent function module parameters of GX Works2 without
a program. For details of the setting procedure, refer to the manual for each module.
(Setting conditions)
(a) Resolution of the AnS series module: 1/8000 (Only one channel is used.)
(b) L series module: L60AD4
(Example of scaling setting window)
Point
The scaling value (digital operation value) and digital output value of the analog input module are stored
different buffer memory addresses, therefore, the scaling value of each channel needs to be read from
the buffer memory.
Present value
read condition
s manual.
'
1/4000
Selectable
1/8000
1/12000
(The resolution differs depending on analog input range.)
FROMP
H0
K54
: Measure required by user,
Resolution of L series analog I/O module
When analog input range is 0 to 10V
L60AD4: 1/20000
L60ADVL8: 1/16000
Read the scaling value (digital
operation value) of Channel 1
D0
K1
from the buffer memory.
: Measure not required by user
*1*2
*1*2
*1*2