A1S63Ada; Performance Specifications Comparison - Mitsubishi Electric MELSEC L Series Manual

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

4
ANALOG I/O MODULE REPLACEMENT

4.2 A1S63ADA

4.2.1 Performance specifications comparison

Item
Number of analog input points
Voltage
Analog input
Current
Digital output
I/O characteristics
Resolution
Overall accuracy
(Accuracy for the maximum digital
output value)
Maximum conversion speed
Absolute maximum input
4
- 3
A1S63ADA
2 channels/module
-10 to 0 to 10VDC (Input resistance value: 1M)
-20 to 0 to 20mA (Input resistance value: 250)
16-bit signed binary
1/4000 setting: -4096 to 4095
1/8000 setting: -8192 to 8191
1/12000 setting: -12288 to 12287
Analog input
10V
5V
20mA
I/O
0V
characteristics
4mA
-5V
-12mA
-10V
Voltage input
Resolution
Current input
1/4000 setting: ±40
1/8000 setting: ±80
1/12000 setting: ±120
1/4000 setting: 1ms/channel
1/8000 setting: 2ms/channel
1/12000 setting: 3ms/channel
Voltage: ±15V
Current: ±28mA
Digital output value
(when gain 5V/20mA, offset 0V/0mA)
1/4000
1/8000
1/12000
4000
8000
2000
4000
0
0
-2000
-4000
-4000
-8000
2.5mV
1.25mV
0.83mV
10µA
5µA
3.33µA
±1%
12000
6000
0
-6000
-12000

Advertisement