Frequency 2
36 Rated frequency f [Hz]
37 Rated voltage / range U [V]
38 Rated current I
39 Power factor cos φ
40 Circuit, graphical symbols according to DIN EN 60617 Part 6 / IEC 60617-6
41 Rated power P N [kW], duty type (if ≠ S1)
42 Efficiency class marking
43 Rated speed n
44 Motor designation, active part
● If you use the STARTER commissioning tool and a SIEMENS motor, you only need to
specify the order number of the motor, otherwise you must note the data from the motor
rating label.
● Pay attention to the connection of the motor (star connection [Y] or delta connection [Δ] ).
Note the appropriate motor data for connecting.
● Motor ambient temperature if it differs from the factory setting = 20° C.
5.2.1.2

Inverter factory setting

Motor
With its factory settings, the inverter is set up for an induction motor suitable for the power
rating of the Power Module.
Inverter control
You will find the factory setting of the inverter control in chapter: Inverter control (Page 163)
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
[A]
N
[rpm]
N
Commissioning
5.2 Basic commissioning
87