Figure 6-3
As previously mentioned, parameter p0756 can be modified to change the type of analog
input. The default settings for parameter p0756 and its default settings are given in the
following table.
Analog input
AI0
AI1
The complete settings available for parameter p0756 are shown below.
0:
1:
2:
3:
9:
You can define your own characteristic that matches your particular application. The linear
scaling characteristic is defined using two points (p0757, p0758) and (p0759, p0760).
Parameters p0757 ... p0760 are assigned to an analog input via their index, e.g. parameters
p0757[0] ... p0760[0] belong to analog input 0.
Figure 6-4
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Analog DIP Switch
Unipolar voltage input
Unipolar voltage input
Unipolar voltage input
Unipolar voltage input moni-
tored
Unipolar current input
Unipolar current input moni-
tored
Unipolar voltage input
Scaling characteristics
Value range
0 V ... +10 V
0 V ... + 10 V
Adapt inputs and outputs
6.2 Analog inputs
Parameter default settings
p0756 [0] = 0
p0756 [1] = 0
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
0 V ... +3 V
121