11.5

List of alarms and faults

Axxxxx Alarm
Fyyyyy: Fault
Table 11- 6
Faults, which can only be acknowledged by switching the inverter off and on again
Number
Cause
F01000
Software fault in CU
F01001
Floating Point Exception
F01015
Software fault in CU
F01018
Power-up aborted more than once
F01040
Parameters must be saved
F01044
Loading of memory data card de-
fective
F01105
CU: Insufficient memory
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to
establish an conversion factor for
scaling which is not present
F01662
CU hardware fault
F30022
Power Module: Monitoring U
F30052
Incorrect Power Module data
F30053
Error in FPGA data
F30662
CU hardware fault
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Format
Visible String
[20]
Visible String
[16]
u16
char, u8[3]
u16
u16
u16
u8[2]
bit[16]
Remedy
Replace CU.
Switch CU off and on again.
Upgrade firmware or contact technical support.
After this fault is output, the inverter powers up with the factory settings.
Remedy: Back up factory setting with p0971=1. Switch CU off and on
again. Recommission the inverter.
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Reduce number of data records.
Contact technical support.
Replace CU.
Create scaling or check transfer value.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Check or replace the Power Module.
CE
Replace Power Module or upgrade CU firmware.
Replace the Power Module.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Alarms, faults and system messages
11.5 List of alarms and faults