Installation
4.2 System Installation
13. Fitting the blanking plate
1. Using the four screws, fit the blank plate to the side of the termi-
nal housing.
2. Ensure that no cables or components are trapped between the
blanking plate and the terminal housing seal, as this would ad-
versely affect the IP rating of the terminal housing.
Note:
Screws tightening torque: 1.5 Nm.
14. Fitting the Control Module
1. Ensuring that no wiring is trapped by the Control Module, place
the module on the four supporting posts of the terminal housing.
2. Using the four screws (self-retaining), secure the Control Module
into place.
Note:
Screws tightening torque: 1.5 Nm.
15. Fitting the Communications and Power Interface (CPI)
1. Using the four screws, fit the CPI to the side of the terminal hous-
ing.
2. Ensure that no cables or components are trapped between the
CPI and the terminal housing seal, as this would adversely affect
the IP rating of the terminal housing.
Notes:
Screws tightening torque: 1.5 Nm.
The Communications and Power Interface (CPI) can be fitted on
the left or right side of the terminal housing, but must always be
fitted on the opposite side of the terminal housing from the inter-
nal braking resistor.
50
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD