Number
Cause
A07991
Motor data identification activated
F08501
Setpoint timeout
F08502
Monitoring time sign-of-life expired
F08510
Send configuration data not valid
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting adjust-
able parameters
F13100
Know-how protection: Copy protec-
tion error
F13101
Know-how protection: Copy protec-
tion cannot be activated
F30001
Overcurrent
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Remedy
Switch on the motor and identify the motor data.
Check the PROFINET connection.
•
Set the controller to RUN mode.
•
If the error occurs repeatedly, check the set monitoring time p2044.
•
Check the PROFINET connection.
•
Check the PROFINET configuration
•
Activate the controller with cyclic operation.
•
Check the parameters "Name of Station" and "IP of Station" (r61000,
•
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
•
IP address or station name used twice in the network.
•
Station name contains invalid characters.
•
The know-how protection and the copy protection for the memory card
are active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
•
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
•
Insert a valid memory card.
Check the following:
Motor data, if required, carry out commissioning
•
Motor connection method (Υ / Δ)
•
U/f operation: Assignment of rated currents of motor and Power Mod-
•
ule
Line quality
•
Make sure that the line commutating reactor is connected properly
•
Power cable connections
•
Power cables for short-circuit or ground fault
•
Power cable length
•
Line phases
•
If this doesn't help:
U/f operation: Increase the acceleration ramp
•
Reduce the load
•
Replace the power unit
•
Alarms, faults and system messages
11.5 List of alarms and faults
301