Data sets
A.3 DS73 logbook - Read triggering operations
A.3

DS73 logbook - Read triggering operations

Byte
0 ... 3
4 ... 5
6 ... 9
10 ... 11
...
...
120 ... 123
124 ... 125
The data set call "Logbook trips" returns the operating hour of the event that has occurred
and an associated object number for each entry. This data set can accommodate 21 entries.
When all locations have been overwritten, the oldest entry is overwritten again.
Note
The latest entry is entered at the first location of the data set. The remaining entries are
moved one entry down. You cannot delete the logbook.
122
Data type
Meaning
Unsigned 32 Operating hours - device
Signed 16
Object number
Entry 2 (second-latest entry)
Unsigned 32 Operating hours - device
Signed 16
Object number
Entry 21 (last, oldest entry)
Unsigned 32 Operating hours - device
Signed 16
Object number
Entry 1 (latest entry)
Manual, 12/2016, A5E34821005002A/RS-AB/002
Range of values
Increment
0 ... 2
-1
1 s
32
0 ... ±32767
0 ... 2
-1
1 s
32
0 ... ±32767
0 ... 2
-1
1 s
32
0 ... ±32767
Motor starter (3RK1308-0**00-0CP0)