Summary of Contents for Siemens SIMATIC ET 200SP

  • Page 2 ___________________ Digital output module Preface DQ 8x24VDC/0.5A ST ___________________ Documentation guide (6ES7132-6BF00-0BA0) ___________________ Product overview SIMATIC ___________________ Wiring up ET 200SP ___________________ Digital output module Parameters/address space DQ 8x24VDC/0.5A ST ___________________ (6ES7132-6BF00-0BA0) Interrupts/diagnostics alarms ___________________ Technical specifications Manual ___________________ Parameter data record 07/2014 A5E03574575-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 5: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................6 Product overview ............................ 8 Properties ............................8 Wiring up .............................. 10 Terminal assignment ........................10 Schematic circuit diagram ......................11 Parameters/address space ........................12 Parameters ........................... 12 Explanation of the parameters ..................... 14 Address space ..........................
  • Page 6: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC distributed I/O system.
  • Page 7 Documentation guide Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942). My Documentation Manager The My Documentation Manager is used to combine entire manuals or only parts of these to your own manual.
  • Page 8: Product Overview

    Product overview Properties Article number 6ES7132-6BF00-0BA0 View of the module Figure 2-1 View of the module DQ 8×24VDC/0.5A ST Properties The module has the following technical properties: ● Digital output module with 8 outputs ● Supply voltage L+ ● Output current 0.5 A per channel ●...
  • Page 9 ● Color identification labels ● Reference identification label ● Shield connector See also You can find additional information on the accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0) Manual, 07/2014, A5E03574575-AC...
  • Page 10: Wiring Up

    The first BaseUnit of an ET 200SP station must be a light-colored BaseUnit. Also keep this in mind during the configuration. You will find additional information on the BaseUnit types in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0) Manual, 07/2014, A5E03574575-AC...
  • Page 11: Schematic Circuit Diagram

    Wiring up 3.2 Schematic circuit diagram Schematic circuit diagram Schematic circuit diagram Figure 3-1 Block diagram DQ 8×24VDC/0.5A ST Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0) Manual, 07/2014, A5E03574575-AC...
  • Page 12: Parameters/Address Space

    Parameters/address space Parameters Parameters for DQ 8x24VDC/0.5A ST The effective range of the parameters depends on the type of configuration. The following configurations are possible: ● Central operation with an S7-1500 CPU ● Distributed operation on PROFINET IO in an ET 200SP system ●...
  • Page 13 Parameters/address space 4.1 Parameters Parameters Value range Default Configuration Effective range in RUN with configuration software, e.g. STEP 7 (TIA Portal) GSD file GSD file PROFINET IO PROFIBUS DP Substitute value Channel Channel • • Potential group Use potential Module Module Use potential group •...
  • Page 14: Explanation Of The Parameters

    Specifies the behavior of the module if the CPU changes to STOP. Potential group Specifies that a BaseUnit with voltage supply feed-in is located in this slot (see system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293)). Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0) Manual, 07/2014, A5E03574575-AC...
  • Page 15: Address Space

    Parameters/address space 4.3 Address space Address space Configuration options The following configurations are possible: ● Configuration 1: Without value status ● Configuration 2: With value status Evaluating the value status An additional byte is allocated in the input address space if you enable the value status for the digital module.
  • Page 16: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error display LED display The figure below shows the LED displays of the DQ 8x24VDC/0.5A ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED display Meaning of the LED displays The following tables show the meaning of the status and error displays. Measures for dealing with diagnostics alarms can be found in the section Diagnostics alarms (Page 19).
  • Page 17 Interrupts/diagnostics alarms 5.1 Status and error display DIAG LED Table 5- 1 DIAG LED fault/error display DIAG LED Meaning Backplane bus supply of the ET 200SP not OK off 
 Module parameters not assigned Flashes Module parameters assigned and no module diagnostics Module parameters assigned and module diagnostics Flashes Channel status LED...
  • Page 18: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The digital output module DQ 8×24VDC/0.5A ST supports diagnostics interrupts. Diagnostics interrupt The module generates a diagnostics interrupt for the following events: ● Channel temporarily unavailable ● Short-circuit ● Wire break ● Parameter assignment error ●...
  • Page 19: Diagnostics Alarms

    Interrupts/diagnostics alarms 5.3 Diagnostics alarms Diagnostics alarms A diagnostics alarm is output for each diagnostics event and the DIAG LED on the module flashes. The diagnostics alarms can, for example, be read from the diagnostics buffer of the CPU. You can evaluate the error codes with the user program. Table 5- 4 Diagnostics alarms, their meaning and how to deal with them Diagnostics alarm...
  • Page 20: Technical Specifications

    Technical specifications Technical specifications Technical specifications of DQ 8×24VDC/0.5A ST 6ES7132-6BF00-0BA0 Product type designation DQ 8x24VDC/0.5A ST General information Firmware version V1.1 Usable BaseUnits BU type A0 Color code for module-specific color identification label CC02 Product function I&M data Engineering with STEP 7 TIA Portal can be configured/integrated as of version V11 SP2 / V13 STEP 7 can be configured/integrated as of version V5.5 SP3 / -...
  • Page 21 Technical specifications 6.1 Technical specifications 6ES7132-6BF00-0BA0 Hardware configuration Fieldbus connection via separate transceiver Digital outputs Number of outputs Sourcing output Short-circuit protection 0.7 to 1.3 A Response threshold, typ. • Limitation of inductive shutdown voltage to Typ. L+ (-50 V) Control of a digital input Switching capacity of outputs With resistive load, max.
  • Page 22 Technical specifications 6.1 Technical specifications 6ES7132-6BF00-0BA0 Diagnostics alarms Monitoring of supply voltage Wire break Short-circuit Group error Diagnostics display LED Monitoring of the supply voltage (PWR LED) Yes; green PWR LED Channel status display Yes; green LED For module diagnostics Yes;...
  • Page 23 "0" signal state at the output, which may cause the display diodes to flicker. This residual current depends on the setting for the Diagnostics: Wire break parameter. Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0) Manual, 07/2014, A5E03574575-AC...
  • Page 24: Parameter Data Record

    Parameter data record Parameter assignment and structure of the parameter data record Parameter assignment in the user program You can change the parameters of the module in RUN. Changing parameters in RUN The "WRREC" instruction is used to transfer the parameters to the module using data record 128.
  • Page 25 Parameter data record A.1 Parameter assignment and structure of the parameter data record Structure of data record 128 Note Channel 0 contains the diagnostics for the entire module. Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0)
  • Page 26 Parameter data record A.1 Parameter assignment and structure of the parameter data record Parameters The figure below shows the structure of the parameters for channels 0 to 7. You enable a parameter by setting the corresponding bit to "1". Figure A-3 Structure byte x to x+1 for the channels 0 to 7 Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0) Manual, 07/2014, A5E03574575-AC...