Data formats and data records
D.3.4
Data record 73 – read logbook – trips
Byte
0...3
Hours of operation –
device
4...5
ID number device error
..
120...
Hours of operation –
123
device
124...
ID number trip
125
Table D-6: Data record 73 – read logbook – trips
The data record can contain 21 entries. When all the places have been written,
the first entry is overwritten.
Note
The newest entry is entered at the end of the data record. The remaining
entries are shifted up by one entry.
The following signals can be entered:
ID no.
309
Switching element overload
317
Supply voltage for electronics too low
318
Supply voltage for switching element missing
319
Mains voltage lost
323
intermediate circuit voltage too high
324
Temperature sensor overload
325
Temperature sensor wire break
326
Temperature sensor short circuit
327
Thermal motor model overload
331
Line protection overload
334
I
limit value exceeded
e
335
I
limit value undershot
e
338
Residual current tripping
339
Motor block tripping
341
Asymmetry tripping
343
Earth fault tripping
348
Input tripping
Table D-7: Read signals in the logbook – trips
D-12
Meaning
Value range
1...4294967295
0...32767 signed 16 1
1...4294967295
0...32767 signed 16 1
Trips – signals
Increment
Note
1 s
Oldest
entry
1 s
Last,
latest
entry
Note
SIMATIC - ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04