DS94 Read measured values

Object
No.
504
505
506
-
503
502
-
513
514
515
516
-
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
Byte.Bit
Meaning
50.0
Explosion protection of the motor active
50.1
Reserved
50.2
New safety-related parameters received
50.3-7
Reserved
51
Reserved
52.0-3
Reserved
52.4
I
warning limit exceeded
e
52.5
I
warning limit undershot
e
52.6-7
Reserved
53
Reserved
Byte.Bit
Coding
0
Unsigned 8
1
Unsigned 8
2
Unsigned 8
3 ... 6
0x00
7
Unsigned 8
8 ... 9
Unsigned 16
10 ... 27
0x00
28 ... 31
Signed 32
32 ... 35
Signed 32
36 ... 39
Signed 32
40 ... 41
Unsigned 16
42 ... 63
0x00
Ex motor protection
Warnings
Meaning
User data (technology data)
Measured values (volatile)
Phase current I
L1(%)
Phase current I
L2(%)
Phase current I
L3(%)
Reserved
Unbalance
Motor heating
Reserved
Phase current I
L1(rms)
Phase current I
L2(rms)
Phase current I
L3(rms)
Electronics supply voltage
Reserved
A.6 DS94 Read measured values
Relevant for
Fail-safe motor
starters only
-
-
-
-
-
All
All
-
-
Range of values
Increment
0 ... 796 %
3.125 %
0 ... 796 %
3.125 %
0 ... 796 %
3.125 %
-
-
0 ... 255 %
1 %
0 ... 1,000 %
1 %
-
-
±0 ... 20,000 A
0.01 A
±0 ... 20,000 A
0.01 A
±0 ... 20,000 A
0.01 A
0 ... 1,500 V
0.1 V
-
-