Maintenance - Siemens SIMATIC ET 200SP Manual

Motor starter (3rk1308-0**00-0cp0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Alarms/diagnostic messages

5.4 Maintenance

Error type
channel
diagnostics
1095
1096
109D
109E
109F
10A5
5.4
Maintenance
A maintenance alarm is output for each group warning and the MT LED lights up on the
module when group warning diagnostics are enabled. You can read out the diagnostic
messages in the diagnostics buffer of the CPU, for example. You read the maintenance
alarms in data set 75 (Page 124) of the motor starter.
Extended maintenance
You will find general information on extended maintenance in "Diagnostics" in the SIMATIC
PROFINET Function Manual
(https://support.industry.siemens.com/cs/de/de/view/49948856/en).
The PROFINET interfaces of the interface module support the diagnostics concept and
maintenance concept in PROFINET according to the standard IEC 61158-6-10. The aim is
early detection and correction of potential faults. The motor starter's full functionality
(maintenance) is available with firmware version V3.3 of the interface module.
The maintenance information is generated in STEP 7 with the following system messages:
● Maintenance request - symbolized by a yellow screwdriver.
● Faults - symbolized by a red screwdriver
See also
SIMATIC ET 200SP System Manual
(http://support.automation.siemens.com/WW/view/en/58649293)
116
Fault text
Parameterization error
h
Process image error
h
Input Action
h
Emergency end position
h
CW
Emergency trip end
h
position CCW
Phase failure or fuse
h
defective
Remedial measures
The module is not yet parameterized or is incorrectly
parameterized or the safety-related parameters have been
rejected.
Remedy: Correct the parameterization.
The process image output (PIQ) contains invalid control bit
combinations (e.g. control bits for clockwise and counter-
clockwise set simultaneously).
Remedy: Check and correct the process image output
(PIQ).
A warning or trip signal is active on at least one input.
Remedy: Check the application.
The "CW" emergency end position has been passed.
Remedy: Check the end position of the drive.
The "CCW" emergency end position has been passed.
Remedy: Check the end position of the drive.
Possible causes: Phase failure, fault in the motor winding,
fuse in the device defective
Remedy: Check the motor feeder (main circuit) and the
motor. Clear the short-circuit in the system and replace the
device.