Siemens SIMATIC ET 200SP Manual page 132

Motor starter (3rk1308-0**00-0cp0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Data sets
A.8 Read/write DS201 device parameter 1
Object
Byte.Bit
Range of values
No.
[0]: Enable
193
2.3
[1]: Disable
[0]: Non-retentive
80
2.4
[1]: Retentive
81
2.5
See input 1 signal
82
2.6
See input 1 signal
191
2.7
[0]: Enable
[1]: Disable
194
3
[0]: No action
[1]: Trip without restart
[2]: Trip with restart
[3]: Trip end position CW
[4]: Trip end position CCW
[5]: Group warning
[7]: Emergency start (not during ATEX
operation)
[8]: Motor CW
[9]: Motor CCW
[11]: Quick Stop (direction-independent)
[12]: Trip RESET
[13]: Cold start (not during ATEX
operation)
[14]: Quick Stop clockwise
[15]: Quick Stop counter-clockwise
[37]: Operational trip end position CW
[38]: Operational trip end position CCW
195
4
See input 1 - action
[9]: Motor CCW (default for reversing
starters)
196
5
See input 1 - action
[13]: Cold start (default for standard
motor starters)
2
6 - 7
0.3 ... 12 A/10 mA
The maximum current is preset.
15
8
18.75 ... 100 %/3.125 % [6 ... 32]
[0]: Deactivated
16
9
50 ... 400 %/3.125 % [16 ... 128]
[0]: Deactivated
132
Meaning
Group fault diagnostics
Input 1 signal
Input 2 signal
Input 3 signal
Group warning diagnostics
Input 1 action
Input 2 action
Input 3 action
Rated operational current I
The rated operational
current is MLFB-dependent,
and thus also the maximum
setting range.
Lower current limit
Upper current limit
Manual, 12/2016, A5E34821005002A/RS-AB/002
See Chapter ...
Group fault
diagnostics/group warning
diagnostics (Page 64)
Inputs (Page 65)
Inputs (Page 65)
Inputs (Page 65)
Group fault
diagnostics/group warning
diagnostics (Page 64)
Inputs (Page 65)
Inputs (Page 65)
Inputs (Page 65)
Rated operational current
e
(Page 35)
Upper/lower current limit
(Page 55)
Upper/lower current limit
(Page 55)
Motor starter (3RK1308-0**00-0CP0)