4.3
Parameterization using a GSD file
For the SIMATIC ET 200SP motor starter, there are two different GSD files, one for
operation with PROFINET, and one for operation with PROFIBUS. The GSD and GSDML
files can be used with STEP 7 V5.5 SP4 and higher, and TIA Portal V13 SP1 and higher.
If you configure the SIMATIC ET 200SP motor starter in the PROFIBUS environment with
GSD, and the standard values in data set 202 have to be changed, then you create data set
202 via the user program on initial commissioning of the starter. Transfer the data set to the
PLC.
Parameterization with the PROFINET GSDML file
With the GSDML file for PROFINET, the SIMATIC ET 200SP motor starter can be fully
configured with all parameters.
Parameterization with the PROFIBUS GSD file
Two parameter data sets (DS201 and DS202) are used for configuring the SIMATIC
ET 200SP motor starter. Only data set DS 201 is ever transferred as the startup data set
when using a PROFIBUS GSD.
4.4
Slot rules
You can find further information on the structure of a system with an ET 200SP motor starter
in the the ET 200SP System Manual
(http://support.automation.siemens.com/WW/view/en/58649293).
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
Parameters/address space
4.3 Parameterization using a GSD file