Summary of Contents for Siemens SIMATIC ET 200SP

  • Page 2 ___________________ Preface ___________________ Guide ___________________ SIMATIC Product overview ___________________ BusAdapter BA 2xRJ45 ET 200SP BusAdapter ___________________ BusAdapter BA 2xFC ___________________ BusAdapter BA 2xSCRJ Manual ___________________ BusAdapter BA SCRJ/RJ45 ___________________ BusAdapter BA SCRJ/FC ___________________ BusAdapter BA 2xLC ___________________ BusAdapter BA LC/RJ45 ___________________ BusAdapter BA LC/FC ___________________...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Table of contents Preface ..............................5 Guide ..............................8 BusAdapter guide ........................8 Product overview ..........................11 BusAdapter BA 2xRJ45......................... 14 Product overview ........................14 Connecting ..........................15 Diagnostics ..........................18 Technical specifications ......................19 BusAdapter BA 2xFC ..........................20 Product overview ........................
  • Page 5 Table of contents BusAdapter BA 2xLC ..........................47 Product overview........................47 Connecting ..........................48 Diagnostics ..........................52 Technical specifications ......................53 BusAdapter BA LC/RJ45 ........................54 10.1 Product overview........................54 10.2 Connecting ..........................55 10.3 Diagnostics ..........................57 10.4 Technical specifications ......................58 BusAdapter BA LC/FC ..........................
  • Page 6: Preface

    Preface Purpose of the manual This manual provides all the necessary information for configuring, installing, connecting and commissioning the BusAdapter. Basic knowledge required The following knowledge is required in order to understand the manual: ● General knowledge in the field of automation technology ●...
  • Page 7 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 8 This information is provided by the Siemens Industry Online Support on the Internet (http://www.siemens.com/automation/service&support). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 9: Guide

    Documentation area. Furthermore, your data is automatically filled into support requests and you always have an overview of your current requests. You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/de/). BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 10 You can export the manual in PDF format or in an editable format. Your documentation is available in My Documentation Manager (http://support.industry.siemens.com/My/ww/de/documentation). "mySupport" - CAx data In the CAx data area in "mySupport", you can access the current product data for your CAx or CAe system.
  • Page 11 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/de/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
  • Page 12: Product Overview

    Product overview Introduction The SIMATIC BusAdapters connect PROFINET IO to their ET 200SP system. You select the required connection technology and connection method for your process from the different versions of SIMATIC BusAdapter. Supported PROFINET devices The SIMATIC BusAdapters are used for: ●...
  • Page 13 Product overview BusAdapter Article number Property Figure BA 2xSCRJ 6ES7193-6AP00- PROFINET BusAdapter with fiber- 0AA0 optic cable connection POF/PCF for SCRJ connector for applica- tions with increased EMC and vibration/shock load as well as electrical potential differences between two stations 6ES7193-6AP20- Media converter, PROFINET SCRJ/RJ45...
  • Page 14 Product overview BusAdapter Article number Property Figure BA LC/RJ45 6ES7193-6AG20- Media converter, PROFINET 0AA0 BusAdapter with glass fiber-optic cable ⇔ standard RJ45 connector BA LC/FC 6ES7193-6AG40- Media converter, PROFINET 0AA0 BusAdapter with glass fiber-optic cable ⇔ direct connection of bus cable See also Strain relief (Page 64)
  • Page 15: Busadapter Ba 2Xrj45

    BusAdapter BA 2xRJ45 Product overview Article number 6ES7193-6AR00-0AA0 View Figure 4-1 BusAdapter BA 2×RJ45 Properties ● You connect PROFINET IO cable with RJ45 connector to the PROFINET device via the BusAdapter BA 2×RJ45. To do this, screw the BusAdapter BA 2×RJ45 to the PROFINET device and insert the PROFINET connecting cable.
  • Page 16: Connecting

    BusAdapter BA 2xRJ45 4.2 Connecting Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required ● Connector: – IE FC RJ45 plug 180 2X2 (6GK1901-1BB10-2A) –...
  • Page 17 Termination Network 1 Procedure Watch video sequence "Connect BusAdapter BA 2xRJ45 to the ET 200SP interface module" (https://support.industry.siemens.com/cs/ww/de/view/95886218) To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xRJ45, follow these steps: 1. Plug the BusAdapter BA 2×RJ45 into the PROFINET device.
  • Page 18 BusAdapter BA 2xRJ45 4.2 Connecting BusAdapter BA 2×RJ45 installed ① ② BusAdapter BA 2×RJ45 ③ PROFINET connecting cable ④ Interface module Figure 4-2 BusAdapter BA 2×RJ45 installed (using an ET 200SP CPU/interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent).
  • Page 19: Diagnostics

    BusAdapter BA 2xRJ45 4.3 Diagnostics Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA 2xRJ45: ① LK1 (green) ② LK2 (green) Figure 4-3 LEDs on the BusAdapter BA 2xRJ45 LK1/LK2 LEDs on the BusAdapter Table 4- 2 Status and error displays Meaning Remedy...
  • Page 20: Technical Specifications

    BusAdapter BA 2xRJ45 4.4 Technical specifications Technical specifications Technical specifications of the BusAdapter BA 2×RJ45 Article number 6ES7193-6AR00-0AA0 Interfaces Number of PROFINET interfaces PROFINET IO Yes; 2 x RJ 45 • FC (FastConnect) • Number of SCRJ ports • Number of LC ports •...
  • Page 21: Busadapter Ba 2Xfc

    BusAdapter BA 2xFC Product overview Article number 6ES7193-6AF00-0AA0 View Figure 5-1 BusAdapter BA 2xFC Properties ● You connect PROFINET IO cable with FastConnect connection method to the PROFINET device via the BusAdapter BA 2xFC. To do this, screw the BusAdapter BA 2xFC with the connected PROFINET connection cable in place on the PROFINET device.
  • Page 22: Connecting

    BusAdapter BA 2xFC 5.2 Connecting Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required ● If you use Fast Connect Cable, we recommend the Industrial Ethernet Fast Connect Stripping Tool (6GK1901-1GA00) with green knife cassette (6GK1901-1B).
  • Page 23 Transmit Data + Procedure Watch the video sequence "Connecting the BusAdapter BA 2xFC to the interface module" (https://support.industry.siemens.com/cs/ww/de/view/95886218) To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xFC, follow these steps: 1. Strip insulation from the sheath of the PROFINET connecting cable as follows:...
  • Page 24 BusAdapter BA 2xFC 5.2 Connecting 5. Close the cover of the connection element. Then push the locking slide forwards as far as it will go. 6. Screw the BusAdapter BA 2×FC to the PROFINET device (1 screw with 0.2 Nm tightening torque).
  • Page 25 BusAdapter BA 2xFC 5.2 Connecting BusAdapter BA 2xFC installed ① ② BA 2xFC BusAdapter ③ PROFINET connecting cable ④ Connection element Figure 5-4 BusAdapter BA 2xFC installed (using an ET 200SP CPU/interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent).
  • Page 26: Diagnostics

    BusAdapter BA 2xFC 5.3 Diagnostics Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA 2xFC: ① LK1 (green) ② LK2 (green) Figure 5-5 LEDs on the BusAdapter BA 2xFC LK1/LK2 LEDs on the BusAdapter Table 5- 2 Status and error displays Meaning Remedy...
  • Page 27: Technical Specifications

    BusAdapter BA 2xFC 5.4 Technical specifications Technical specifications Technical specifications of the BusAdapters BA 2×FC Article number 6ES7193-6AF00-0AA0 Interfaces Number of PROFINET interfaces PROFINET IO Yes; 2 x FC (FastConnect) • Cable length 100 m – Cu conductors Dimensions Width 20 mm Height 69.5 mm...
  • Page 28: Busadapter Ba 2Xscrj

    BusAdapter BA 2xSCRJ Product overview Article number 6ES7193-6AP00-0AA0 View Figure 6-1 BusAdapter BA 2xSCRJ Properties ● Using BusAdapter BA 2×SCRJ , you connect PROFINET IO to the PROFINET device optically with fiber-optic cables via an SCRJ connector. To do this, screw the BusAdapter BA 2×SCRJ to the PROFINET device and plug in the SCRJ connector.
  • Page 29: Connecting

    BusAdapter BA 2xSCRJ 6.2 Connecting Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required ● Connector for PROFINET connection: IE SCRJ POF Plug ●...
  • Page 30 BusAdapter BA 2xSCRJ 6.2 Connecting Requirements ● Prepare the IE POF cables with the connectors IE SCRJ POF Plug or IE SC RJ PCF Plug. You will find more Instructions in the installation instructions: – POF fiber-optic cables with IE SCRJ POF plugs (A5E00351141). –...
  • Page 31 BusAdapter BA 2xSCRJ 6.2 Connecting Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA 2×SCRJ. Table 6- 1 PROFINET IO pin assignment with BusAdapter BA 2×SCRJ View Sig- Description name ① Receive Data ②...
  • Page 32 This will prevent any attenuation losses caused by re-bent, heavily stressed portions of the fiber-optic cores. Reference For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC NET PROFIBUS Network Manual (https://support.industry.siemens.com/cs/de/de/view/1172302). BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 33: Diagnostics

    BusAdapter BA 2xSCRJ 6.3 Diagnostics Diagnostics LEDs The figure below shows the LED display on the BusAdapter BA 2xSCRJ: ① LK1 (green) ② MT1 (yellow) ③ LK2 (green) ④ MT2 (yellow) Figure 6-3 LEDs on the BusAdapter BA 2xSCRJ BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 34 BusAdapter BA 2xSCRJ 6.3 Diagnostics LK1/LK2 and MT1/MT2 LEDs on the BusAdapter Table 6- 2 Status and error displays Meaning Remedy LK1/LK2 MT1/MT2 Not relevant There is no Ethernet connection Check whether the bus cable to the switch or between the PROFINET IO interface IO controller is disconnected.
  • Page 35: Technical Specifications

    BusAdapter BA 2xSCRJ 6.4 Technical specifications Technical specifications Technical specifications of BusAdapter BA 2×SCRJ Article number 6ES7193-6AP00-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (switch) SCRJ FO PROFINET IO RJ 45 • FC (FastConnect) • Number of SCRJ ports •...
  • Page 36: Busadapter Ba Scrj/Rj45

    BusAdapter BA SCRJ/RJ45 Product overview Article number 6ES7193-6AP20-0AA0 View ① Fiber-optic cable SCRJ ② RJ45 Figure 7-1 BusAdapter BA SCRJ/RJ45 Properties You connect PROFINET IO connection cables to the PROFINET device via the BusAdapter BA SCRJ/RJ45: ● Optically with fiber-optic cables (FOC) with an SCRJ connector to port 1 ●...
  • Page 37: Connecting

    BusAdapter BA SCRJ/RJ45 7.2 Connecting Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Connecting the SCRJ connector You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2×SCRJ (Page 28).
  • Page 38 BusAdapter BA SCRJ/RJ45 7.2 Connecting BA SCRJ/RJ45 BusAdapter mounted ① Interface module ② BusAdapter BA SCRJ/RJ45 ③ PROFINET connecting cable Figure 7-2 Connecting the BusAdapter BA SCRJ/RJ45 to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent).
  • Page 39: Diagnostics

    BusAdapter BA SCRJ/RJ45 7.3 Diagnostics Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA SCRJ/RJ45: ① LK1 (green) ② MT (yellow) ③ LK2 (green) Figure 7-3 LED displays on the BusAdapter BA SCRJ/RJ45 BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 40 BusAdapter BA SCRJ/RJ45 7.3 Diagnostics LK1/LK2 and MT LEDs on the BusAdapter Table 7- 2 Status and error displays Meaning Remedy LK1/LK2 Not relevant There is no Ethernet connection Check whether the bus cable to the switch or between the PROFINET IO interface IO controller is disconnected.
  • Page 41: Technical Specifications

    BusAdapter BA SCRJ/RJ45 7.4 Technical specifications Technical specifications Technical specifications of BusAdapter BA SCRJ/RJ45 Article number 6ES7193-6AP20-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (SCRJ + RJ45) PROFINET IO Yes; 1x RJ 45 • FC (FastConnect) • Number of SCRJ ports •...
  • Page 42: Busadapter Ba Scrj/Fc

    BusAdapter BA SCRJ/FC Product overview Article number 6ES7193-6AP40-0AA0 View ① SCRJ fiber-optic cable ② FastConnect FC Figure 8-1 BusAdapter BA SCRJ/FC Properties ● You connect PROFINET IO to the PROFINET device via the BusAdapter BA SCRJ/FC . ● The BusAdapter BA SCRJ/FC has one port for connection of a copper cable and one port for connection of a fiber-optic cable.
  • Page 43: Connecting

    BusAdapter BA SCRJ/FC 8.2 Connecting Connecting Installing the bus connector Install the PROFINET connector according to the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Connecting the SCRJ connector You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2×SCRJ (Page 28).
  • Page 44 BusAdapter BA SCRJ/FC 8.2 Connecting Procedure To connect PROFINET IO to the PROFINET device via the BusAdapter BA SCRJ/FC, follow these steps: 1. Plug the BusAdapter BA SCRJ/FC into the PROFINET device. 2. Screw the BusAdapter BA SCRJ/FC to the PROFINET device (1 screw with 0.2 Nm tightening torque).
  • Page 45: Diagnostics

    BusAdapter BA SCRJ/FC 8.3 Diagnostics Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA SCRJ/FC: ① LK1 (green) ② MT (yellow) ③ LK2 (green) Figure 8-3 LEDs on the BusAdapter BA SCRJ/FC BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 46 BusAdapter BA SCRJ/FC 8.3 Diagnostics LK1/LK2 and MT LEDs on the BusAdapter Table 8- 2 Status and error displays Meaning Remedy LK1/LK2 Not relevant There is no Ethernet connec- Check whether the bus cable to the tion between the switch or IO controller is disconnect- PROFINET IO interface of your PROFINET device and a communication partner, e.g.
  • Page 47: Technical Specifications

    BusAdapter BA SCRJ/FC 8.4 Technical specifications Technical specifications Technical specifications of BusAdapter BA SCRJ/FC Article number 6ES7193-6AP40-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (SCRJ + FC) PROFINET IO RJ 45 • Yes; 1x FC (FastConnect) • Number of SCRJ ports •...
  • Page 48: Busadapter Ba 2Xlc

    BusAdapter BA 2xLC Product overview Article number 6ES7193-6AG00-0AA0 View Figure 9-1 BusAdapter BA 2xLC Properties ● You connect PROFINET IO fiber-optic cables to the PROFINET device via the BusAdapter BA 2×LC. To do this, screw the BusAdapter BA 2×LC to the PROFINET device and insert the PROFINET connection cable.
  • Page 49: Connecting

    BusAdapter BA 2xLC 9.2 Connecting Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Tools required 3 to 3.5 mm screwdriver, alternatively TX10 (torx). Accessories required ● If you prepare the FC FO cables with the IE FC FO LC plug, we recommend the FC FO Termination Kit (LC) (6GK1900-0RL00-0AA0).
  • Page 50 BusAdapter BA 2xLC 9.2 Connecting Pin assignment The following table shows the signal name and description of the pin assignment of BusAdapter BA 2×LC: Table 9- 1 PROFINET IO pin assignment with BusAdapter BA 2xLC View Sig- Description name ① Receive Data ②...
  • Page 51 BusAdapter BA 2xLC 9.2 Connecting Procedure To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xLC, follow these steps: 1. Plug the BusAdapter BA 2xLC into the PROFINET device. 2. Screw the BusAdapter BA 2xLC to the PROFINET device (1 screw with 0.2 Nm tightening torque).
  • Page 52 This will prevent any attenuation losses caused by re-bent, heavily stressed portions of the fiber-optic cores. Reference For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC NET PROFIBUS Network Manual (https://support.industry.siemens.com/cs/de/de/view/1172302). BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 53: Diagnostics

    BusAdapter BA 2xLC 9.3 Diagnostics Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA 2xLC: ① LK1 (green) ② LK2 (green) Figure 9-3 LEDs on the BusAdapter BA 2xLC LK1/LK2 LEDs on the BusAdapter Table 9- 2 Status and error displays Meaning Remedy...
  • Page 54: Technical Specifications

    BusAdapter BA 2xLC 9.4 Technical specifications Technical specifications Technical specifications of BusAdapter BA 2xLC Article number 6ES7193-6AG00-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (switch) LC Multimode Glass Fibre PROFINET IO RJ 45 • FC (FastConnect) • Number of SCRJ ports •...
  • Page 55: Busadapter Ba Lc/Rj45

    BusAdapter BA LC/RJ45 10.1 Product overview Article number 6ES7193-6AG20-0AA0 View ① Glass fiber-optic cable LC ② RJ45 Figure 10-1 BusAdapter BA LC/RJ45 Properties You connect PROFINET IO connection cables to the PROFINET device via the BusAdapter BA LC/RJ45: ● Optically with glass fiber-optic cables with an LC connector to port 1 ●...
  • Page 56: Connecting

    BusAdapter BA LC/RJ45 10.2 Connecting 10.2 Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Attaching LC connectors You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2×LC (Page 48).
  • Page 57 BusAdapter BA LC/RJ45 10.2 Connecting BA LC/RJ45 BusAdapter mounted ① Interface module ② BA LC/RJ45 BusAdapter ③ PROFINET connecting cable Figure 10-2 BusAdapter BA LC/RJ45 installed (using an ET 200SP interface module as an example) Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent).
  • Page 58: Diagnostics

    BusAdapter BA LC/RJ45 10.3 Diagnostics 10.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA LC/RJ45: ① LK1 (green) ② LK2 (green) Figure 10-3 LED displays on the BusAdapter BA LC/RJ45 LEDs LK1/LK2 on the BusAdapter Table 10- 2 Status and error displays Meaning Remedy...
  • Page 59: Technical Specifications

    BusAdapter BA LC/RJ45 10.4 Technical specifications 10.4 Technical specifications Technical specifications of the BusAdapters BA LC/RJ45 Article number 6ES7193-6AG20-0AA0 Interfaces Number of PROFINET interfaces 1; 2 ports (switch) LC / RJ45 PROFINET IO Yes; 1x RJ 45 • FC (FastConnect) •...
  • Page 60: Busadapter Ba Lc/Fc

    BusAdapter BA LC/FC 11.1 Product overview Article number 6ES7193-6AG40-0AA0 View ① Glass fiber-optic cable LC ② FastConnect FC Figure 11-1 BusAdapter BA LC/FC Properties You connect PROFINET IO connection cables to the PROFINET device via the BusAdapter BA LC/FC: ● Optically with glass fiber-optic cables with an LC connector to port 1 ●...
  • Page 61: Connecting

    BusAdapter BA LC/FC 11.2 Connecting 11.2 Connecting Installing the bus connector Install the PROFINET connector in accordance with the instructions in the PROFINET Installation Guide (http://www.profibus.com/). Attaching LC connectors You can find more information about the required tools, accessories, requirements and procedures in the section Connecting BusAdapter BA 2×LC (Page 48).
  • Page 62 BusAdapter BA LC/FC 11.2 Connecting BusAdapter BA LC/FC installed ① Interface module ② BA LC/FC BusAdapter ③ PROFINET connecting cable Figure 11-2 Connecting the BusAdapter BA LC/FC to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV/PELV power supply (or equivalent).
  • Page 63: Diagnostics

    BusAdapter BA LC/FC 11.3 Diagnostics 11.3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA LC/FC: ① LK1 (green) ② LK2 (green) Figure 11-3 LEDs on the BusAdapter BA LC/FC LK1/LK2 LEDs on the BusAdapter Table 11- 2 Status and error displays Meaning Remedy...
  • Page 64: Technical Specifications

    BusAdapter BA LC/FC 11.4 Technical specifications 11.4 Technical specifications Technical specifications of the BusAdapters BA LC/FC Article number 6ES7193-6AG40-0AA0 Interfaces Number of PROFINET interfaces PROFINET IO RJ 45 • Yes; 1x FC (FastConnect) • Number of SCRJ ports • Number of LC ports •...
  • Page 65: Strain Relief

    Strain relief 12.1 Product overview Article number 6ES7193-6RA00-1AN0 (VPE: 5 strain relief units incl. screws) View Figure 12-1 Strain relief Properties ● The strain relief is a mechanical protective device for the electrical PROFINET cables on the BusAdapter. ● The strain relief is suitable for all optical and electrical PROFINET cables of the BusAdapter.
  • Page 66: Installing

    Strain relief 12.2 Installing 12.2 Installing Requirement ● The PROFINET cables are not inserted on the BusAdapter. The inserted PROFINET cables hamper the mounting of the strain relief. ● BusAdapter and strain relief can be mounted separately. Tools required Screwdriver TX10 (torx). Procedure To install the strain relief, follow these steps: 1.
  • Page 67 Strain relief 12.2 Installing 4. Screw the BusAdapter to the PROFINET device (1 screw with 0.2 Nm tightening torque). 5. Attach the PROFINET cables with the cable ties to the strain relief. Figure 12-3 Strain relief installed BusAdapter Manual, 03/2018, A5E41449003-AA...
  • Page 68: Dimension Drawings

    Dimension drawings BusAdapter dimension drawings The figure below shows the dimension drawing of the BusAdapter BA 2xRJ45 as an example. Figure A-1 Dimensional drawing of BusAdapter BA 2xRJ45 Strain relief dimension drawings The figure below shows the dimension drawing of the strain relief. Figure A-2 Strain relief dimension drawing BusAdapter...
  • Page 69: Accessories

    Accessories Accessories Additional accessories are available for the SIMATIC BusAdapters: Accessories Article number Property Figure Strain relief 6ES7193-6RA00- The strain relief is a mechanical 1AN0 protective device for the electrical PROFINET cables on the BusAdapter. The strain relief can be ordered as optional accessories. You install the strain relief on the PROFINET device (e.g.: interface module) before you install the...