Parameters/address space
4.7 Assigning fail-safe motor starter parameters
The start of the flashing sequence is indicated by the "MAN", "F-DI" and "ST/OL" LEDs,
which light up briefly in green all at the same time. The multi-colored LEDs then light up in
red and yellow. Lighting up also serves to verify that all LEDs are functioning correctly.
To signal display of the next parameter, the "ST/OL" LED briefly lights up in red between
every flashing signal for a set parameter.
The flashing sequence ends as soon as you press the blue button twice and confirm the set
parameters.
Note
Receiving several parameter assignments
If safety-related parameters are received during a flashing sequence, conform the first
parameters (or reject them) first. Only then are the parameters that have been sent last
indicated. The motor cannot be started until the parameters last sent are valid and you have
confirmed them.
Rejecting ATEX parameterization
Proceed as follows if you want to reject the set parameterization:
1. Press the blue button for longer than five seconds.
A group fault is output and the "Invalid parameter value" diagnostic message in data set
92 is set. A logbook entry is also created in data set 73. The diagnostic interrupt 0x1095
is also triggered if group fault diagnostics is enabled. In this state you cannot trigger any
of the other functions.
2. Send the correct parameterization via the data set "DS201".
3. Confirm the correct parameterization.
Displaying ATEX parameters
To display the safety-related parameter settings during normal operation, press the
TEST/RESET button for at least five seconds.
See also
DS92 Read device diagnostics (Page 126)
102
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002