4.2 Commissioning mode

Parameters for SIMATIC ET 200SP motor starters
The effective range of the adjustable parameters depends on the type of configuration. The
following configurations are possible:
● Centralized operation with an ET 200SP CPU and the ET 200SP Open Controller
● Distributed operation on the PROFINET IO in an ET 200SP system
● Distributed operation on the PROFIBUS IO in an ET 200SP system
When you assign parameters in the user program, transfer the parameters to the module via
the data sets with the "WRREC" statement.
The parameters that can be set can be found in the Appendix in data set 201 (Page 131)
and data set 202 (Page 133).
You will find an explanation of the parameters in Explanation of the parameters (Page 95).
4.2
Commissioning mode
Commissioning mode is available for fail-safe ET 200SP motor starters.
When setting up a system, you can test the wiring without the functioning PROFINET or
PROFIBUS connection. Perform the test in commissioning mode.
The motor starter switches to commissioning mode in the following cases:
● After the power supply has been activated, the motor starter does not receive any
parameterization via the backplane bus.
● The DI module's "Local Control" switch is activated.
As soon as Local Control is active, the parameterization saved last is used when the
power supply is activated. Control via the DI module is possible after confirmation via the
TEST/RESET button.
To switch to commissioning mode in the case of fail-safe motor starters, confirm the change
with the blue button. During ATEX operation, additionally confirm the current parameters, as
described in chapter "Configuring ATEX operation (Page 100)".
If the motor starter receives valid parameterization via the backplane bus in commissioning
mode, the parameterization is placed in intermediate storage. The parameterization
becomes active when "Local Control" is terminated (motor OFF). The commissioning mode
is exited.
See also
Setting safety-related parameters (Page 98)
92
Motor starter (3RK1308-0**00-0CP0)