Input n action
Different actions can be triggered when an input signal is present. You can parameterize the
following actions dependent on "Input n level", "Input n signal" and "Mode".
Note
If "Input n signal" = retentive, and "Input n action" = Motor CW/CCW, at least one input must
always be parameterized with input action "Tripping ..." or "Quick Stop". If this rule is
violated, the motor starter will reject the parameters with the relevant diagnostics message.
n action
No action
Trip without
restart
Trip with
restart (AUTO
RESET)
Trip end
position CW
Trip end
position CCW
Group
warning
Emergency
start
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
Input
Input
Input
n level
n signal
NO/NC
n. ret./ret.
NO/NC
n. ret.
NO/NC
n. ret.
NO/NC
n. ret.
NO/NC
n. ret.
NO/NC
n. ret./ret.
NO
n. ret.
Operating
mode
All
No direct action on the motor starter. Evaluation
und further processing possible using the process
image.
All
Results in tripping of the motor.
•
Must be acknowledged once the cause of the
•
tripping has been rectified (initial status).
All
Results in tripping of the motor.
•
Acknowledged automatically after the cause
•
of the trip has been rectified (initial status).
All
The motor is switched off regardless of the
•
direction of rotation.
A fault is generated and reported.
•
The motor can only be switched on with
•
"Motor CCW"
All
The motor is switched off regardless of the
•
direction of rotation.
A fault is generated and reported.
•
The motor can only be switched on with
•
"Motor CW"
All
The diagnosis "Group warning" is output.
•
The motor starter is not switched off.
•
All
Starts the load when an ON command is
•
issued despite the fact that an internal trip
command is present.
Intrinsic device protection of the motor starter
•
remains active and prevents the device from
being destroyed.
Only allowed as an NO contact
•
Not parameterizable when the "EX motor"
•
parameter is active.
Product overview
3.7 Functions