B.2.2

F-PM-E tripping

Article numbers:
● BaseUnit: 3RK1908-0AP00-0CP0
● Motor starter: 3RK1308-0C*00-0CP0 or 3RK1308-0D*00-0CP0
● F-PM-E 24 V DC/8A PPM: 6ES7136-6PA00-0BC0
Use F-PME tripping to realize group tripping of several motor starters simultaneously. The F-
PM-E safely switches the motor starter's 24 V power supply. The fail-safe motor starter
safely trips the connected motor load without torque after disappearance of the 24 V power
supply.
In the event of safety shutdown with F-PM-E, there is no detailed diagnosis of the motor
starter via the data sets and the process image of the inputs.
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
B.2 Connection examples for fail-safe motor starters
Circuit examples