4 Faults and alarms
4.2 List of faults and alarms
A07483
EPOS: Travel to fixed stop clamping torque not reached
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The fixed stop in the traversing block was reached without the clamping torque/clamping force having been achieved.
Remedy:
- check the maximum torque-generating current (r1533).
- check the torque limits (p1520, p1521).
- check the power limits (p1530, p1531).
- check the BICO interconnections of the torque limits (p1522, p1523, p1528, p1529).
F07484
EPOS: Fixed stop outside the monitoring window
Message class:
Application/technological function faulted (17)
Reaction:
OFF3 (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
In the "fixed stop reached" state, the axis has moved outside the defined monitoring window (p2635).
Remedy:
- check the monitoring window (p2635).
- check the mechanical system.
F07485 (A)
EPOS: Fixed stop not reached
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
In a traversing block with the task FIXED STOP, the end position was reached without detecting a fixed stop.
Remedy:
- check the traversing block and locate the target position further into the workpiece.
- check the "fixed stop reached" control signal (p2637).
- if required, reduce the maximum following error window to detect the fixed stop (p2634).
A07486
EPOS: Intermediate stop missing
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the modes "traversing blocks" or "direct setpoint input/MDI" at the start of motion, the binector input "no
intermediate stop/intermediate stop" (BI: p2640) did not have a 1 signal.
Remedy:
Connect a 1 signal to the binector input "no intermediate stop/intermediate stop" (BI: p2640) and re-start motion.
See also: p2640 (EPOS intermediate stop (0 signal))
A07487
EPOS: Reject traversing task missing
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the modes "traversing blocks" or "direct setpoint input/MDI" at the start of motion, the binector input "do not reject
traversing task/reject traversing task" (BI: p2641) does not have a 1 signal.
Remedy:
Connect a 1 signal to the binector input "do not reject traversing task/reject traversing task" (BI: p2641) and restart
motion.
See also: p2641 (EPOS reject traversing task (0 signal))
F07488
EPOS: Relative positioning not possible
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
In the mode "direct setpoint input/MDI", for continuous transfer (p2649 = 1) relative positioning was selected (BI:
p2648 = 0 signal).
Remedy:
Check the control.
1094
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890