Note when using the internal resolver evaluation (CU250S):
The nominal signal level is at 1300 mV. The response thresholds are < 490 mV and > 1616 mV.
A signal level of 1300 mV peak value corresponds to the numerical value 2DE6 hex = 11750 dec.
Note:
The analog values of the amplitude error are not measured at the same time with the hardware fault output by the
Sensor Module.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- check that the encoder cables and shielding are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
The following applies to measuring systems without their own bearing system:
- adjust the scanning head and check the bearing system of the measuring wheel.
The following applies for measuring systems with their own bearing system:
- ensure that the encoder housing is not subject to any axial force.
F31116 (N, A)
Encoder 1: Amplitude error monitoring track A + B
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
ENCODER (IASC/DCBRK, NONE)
Acknowledge:
IMMEDIATELY
Cause:
The amplitude of the rectified encoder signals A and B and the amplitude from the roots of A^2 + B^2 for encoder 1
are not within the tolerance bandwidth.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex:
yyyy = Signal level, track B (16 bits with sign).
xxxx = Signal level, track A (16 bits with sign).
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response thresholds are < 130 mV (observe the frequency response of the encoder) and > 955 mV.
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
Note:
The analog values of the amplitude error are not measured at the same time with the hardware fault output by the
Sensor Module.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- check that the encoder cables and shielding are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
F31117 (N, A)
Encoder 1: Inversion error signals A/B/R
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
ENCODER (IASC/DCBRK, NONE)
Acknowledge:
IMMEDIATELY
Cause:
For a square-wave encoder (bipolar, double ended) signals A*, B* and R* are not inverted with respect to signals A,
B and R.
Fault value (r0949, interpret binary):
Bits 0 ... 15: Only for internal Siemens troubleshooting.
Bit 16: Error track A.
Bit 17: Error track B.
Bit 18: Error track R.
Note:
For SMC30 (order number 6SL3055-0AA00-5CA0 and 6SL3055-0AA00-5CA1 only), CUA32, and CU310, the
following applies:
A square-wave encoder without track R is used and track monitoring (p0405.2 = 1) is activated.
See also: p0491 (Motor encoder fault response ENCODER)
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms