4 Faults and alarms
4.2 List of faults and alarms
DI expected states in table format:
Test stop state: Expectation Mode 1 / Mode 2 / Mode 3 / Mode 4
5: -/1/1/-
7: -/0/0/-
9: -/0/1/-
11: -/0/1/-
13: -/1/1/-
Example:
Fault F01773 (P1) is signaled with fault value = 0001_0127 and fault F30773 (P2) is signaled with fault value
0000_0127.
This means that in state 7 (Z = 7) the state of the external readback signal was not set correctly (Y = 2) after DO-0 (X
= 1) was switched to ON/ON.
Fault value 0001_0127 indicates that 0 was expected (W = 0) and 1 (V = 1) was read back from the hardware.
Fault value 0000_0127 on the processor 2 indicates that the states were as expected.
In the case of fault F30773, W and V are always identical; a value of 0 always means that 0 was expected at the
readback input but was not present on processor 1.
Remedy:
Check the wiring of the fail-safe digital output (F-DO) and restart the test stop.
Note:
- the fault is withdrawn if the test stop is successfully completed.
- in the event of multiple test stop faults, the first one that occurred is shown. Once the test stop has been restarted
the next queued test stop fault will be signaled (if there is one).
F-DO: Fail-safe Digital Output
A30788
Automatic test stop: wait for STO deselection via SMM
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The automatic test stop was not able to be carried out after powering up.
Possible causes:
- the STO function is selected via Safety Extended Functions.
- a safety message is present, that resulted in a STO.
Remedy:
- Deselect STO via Safety Extended Functions.
- remove the cause of the safety messages and acknowledge the messages.
The automatic test stop is performed after removing the cause.
C30798
SI Motion P2: Test stop for motion monitoring functions running
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The forced checking procedure (test stop) for the safe motion monitoring functions is currently in progress.
Remedy:
Not necessary.
The message is automatically withdrawn when the test stop has been completed.
Note:
SI: Safety Integrated
C30799
SI Motion P2: Acceptance test mode active
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The acceptance test mode is active.
Remedy:
Not necessary.
The message is withdrawn when exiting the acceptance test mode.